described in the GV2 Arming Without
Passcode Technical Service Note (P/N:
F01U077005).
4.0 Upgrading to a GV2 Series
Control Panel
Remote Programming Software (RPS) version
3.7.160 or above is required to upgrade an
existing G Series Control Panel installation to a
GV2 Series Control Panel. Because the GV2MAIN
and GV2AUX handlers cannot read the
configuration data from a G Series Control Panel,
using RPS is the only method available to convert
an account's existing panel type to a D9412GV2
or D7412GV2.
Refer to the RPS help files for the specific
control panel for additional information on
control panel conversion. In the RPS help file,
select:
Panel Specific Information9000 Series
Control/CommunicatorsCommunicating with
9000 Series PanelsUpgrading a Panel Type
Hardware Enhancements
The control panel has an SDI bus quick-
connect terminal (Molex
the S1 reset switch. This connector provides
an easy way to connect an SDI device to the
SDI bus without disconnecting the wires on
SDI Terminals 29 through 32. To order SDI
wiring harnesses, use the following part
numbers: Molex to Molex (P/N: C321) and
Molex to terminal (P/N: PKWH).
This SDI terminal is not compatible
with the D5200 Programmer.
Two new posts next to the on-board
telephone jack allow easy connection of a
butt set or telephone for troubleshooting
purposes. The posts are labeled TIP and
RING.
The telephone line supervision time
might be affected when a butt set or
telephone is connected to the
telephone terminal posts.
On-board Relays B (Terminal 7, labeled Alt
Alarm) and C (Terminal 8, labeled SW Aux)
are now installed in the factory. No
© 2013 Bosch Security Systems, Inc.
®
connector) next to
D9412GV2/D7412GV2 Release Notes for Version 7.09
D9412GV2/D7412GV2
supplemental installation or purchase is
necessary to prepare these terminals for use.
The battery backed-up RAM now has a Super-
Cap installed. The Super-Cap maintains
power for up to 30 min to the control panel's
memory when replacing the lithium battery.
In earlier G Series control panels, if the coin
battery was removed and the control panel
was powered down, all configuration was
lost. This enhancement allows the control
panel to retain its configuration during
necessary battery replacement.
The D928 line monitor senses trouble if
voltage on the line falls to 5.0 to 7.0 VDC
without a corresponding value of at least 13
mA of current.
The GV2 Series Control Panels now have
integrated watchdog supervision. The D928
Dual Phone Line Switcher is no longer
needed, but is still fully supported.
Page 15