The GV2 Series Control Panels have the same
response to low AC voltage as to an AC
failure.
If the control panel battery is detected as
missing, the Walk Test function skips the
Battery Test.
Several system stability issues are fixed to
prevent erroneous Parameter Checksum
Failures.
The Service Walk Test on the D7412GV2 and
D7212GV2 now shows the correct maximum
number of points in the system.
The Telephone Ground Start circuitry and
associated programming prompts are
removed from the GV2 Series Control Panels.
The GV2 Series Control Panels require the
D6500 receiver to have a D6511 MPU card at
version 1.06 or above for maximum
communication efficiency.
The Extend Close (COMMAND 51) feature
was modified to prevent the new Close
Window time from setting to a value earlier
than the current time.
When disarming an area with Two Man Rule
enabled, the keypad waits for the time equal
to the exit delay for the area. If the second
passcode is not entered before the prompt
times out, then the rule resets and waits for
the first passcode again.
Several changes in this release prevent local
alarm events from being sent intermittently
to the central station. All local alarm events
should now remain local.

2.10 New Features in Version 7.01

Two Man Rule: Two Man Rule requires two
unique passcodes to be entered at the same
keypad to disarm an area. Without the
second passcode, the system denies entry.
Two Man Rule requires the presence of two
people at opening, providing added security.
Early Ambush: Early Ambush requires two
passcode entries on the same keypad or on
two separate keypads located in the same
area. Enter the same passcode twice or enter
two unique passcodes, depending upon the
configuration. The first entry disarms the area
and the second entry stops a timer
programmed to send a duress event. If the
second entry does not occur within the
preset time, the system generates a duress
© 2013 Bosch Security Systems, Inc.
D9412GV2/D7412GV2 Release Notes for Version 7.09
D9412GV2/D7412GV2
event. Early Ambush allows users to inspect
the premises and use the system to confirm
that the area is safe to enter, providing added
security.
Easy Exit Control: The GV2 Series Control
Panels change from one armed state to
another armed state without disarming. For
example, if you change the state from Master
Arm to Perimeter Arm, the control panel
complies and reports the change. Easy Exit
Control reduces the number of keystrokes
and simplifies system operation.
Passcode-controlled Menus: The system
prompts a user to enter a passcode before
viewing the keypad function list menu. The
system shows the user the menu options
allowed according to the user's authority
level. Passcode-controlled menus simplify
system operation by providing a user with
unique and pertinent options and
information. This feature is not intended for
use on D1256 Fire Keypads.
Passcode Follows Scope: Use Passcode
Follows Scope to restrict passcode arming
and disarming only to the keypad's
immediate local area. Passcode Follows
Scope simplifies the arming and disarming
procedure without limiting any other keypad
command capabilities.
Invisible Walk Test: A function list menu
item allows the user to test invisible interior-
or perimeter- controlled and non-controlled
(24-hr) points within the scope of the keypad
without sending a report to the central
station.
Door Activated Custom Function: A custom
function activates when user credentials are
presented to the reader of a D9210B Access
Control Interface Module. A custom function
behaves as though the user performed a
function at the keypad associated with the
door controller. This feature is available only
on the D9412GV2 and D7412GV2.
Latest Close Time: The Extend Close
(COMMAND 51) function is enhanced with a
programmable latest closing time.
Custom Function Enhancements: The
custom functions now support the soft keys
(the eight unmarked keys around the display)
on the D1260 or D1260B Keypads. This