Programming Output Relays

Output Relay Displays
Enter Relay No.
(00 = Quit)
01
02
A EV ZL ZT
STT 0
0
0 00
02
A EV ZL ZT
STP –
0
00
02 Relay Action
No Response
0
02 Start Event
Not Used
0
02 Start:
Zn List
No List
0
02 Start:
Zn Typ
Not Used
00
1. With at least one 2-line Alpha keypad connected to the keypad terminals
on the control, power up the system temporarily. If you had previously
connected the AC transformer to the control panel, you need only plug in
the transformer (to 120VAC outlet) to power up the system.
2. Enter the programming mode by keying the following on the Alpha keypad:
INSTALLER code (4 1 1 1) + 8 + 0.
Program field 25 WIRED EXPANSION/RELAY USED must be programmed
as required before continuing (i.e., 2 = 4229, 3 = 4204).
3
Press 80. Note that this is an interactive menu programming mode. It is
used to program all output relays used in the system (4204 or 4229
modules). Refer to the Programming Form worksheet in the
PROGRAMMING GUIDE for
been programmed for a 4204 or 4229 relay, skip this field.
Upon pressing 80, this screen will appear.
Enter the Relay Number 01, 02, 03, or 04 for a 4204, or 01 or 02 for a 4229
(or 00 to end these entries).
Press the [ ] key to continue.
The [ ] key is used to accept an entry and advance to the next prompt.
The [#] key is used to revert back to the last question to check or change an
entry. Press [ ] to go forward again.
This screen displays a summary of the current Relay START programming
(for this example, relay 02 has been selected).
Press the [ ] key to continue.
This screen displays a summary of the current Relay STOP programming.
Press the [ ] key to continue.
Enter the desired relay action as listed below.
0 = No response
1 = Close for 2 seconds
Press the [ ] key to continue.
Enter the event to START the relay:
0 = Not used; 2 = Fault; 1 = Alarm; 3 = Trouble
A zone list must be used in conjunction with an event. If a zone type/system
operation is to be used instead of an event, enter 0.
Press the [ ] key to continue.
If a zone list will be used to START the relay action, enter the zone list number
(to be programmed in field 81): 1, 2, or 3. If not used, enter 0.
Press the [ ] key to continue.
If a zone type or system operation will be used to START the relay action,
enter the appropriate two-digit code (see table that follows on the next page). If
not, enter 00.
Press the [ ] key to continue.
– 47 –
80 Interactive Mode. If field
2 = Close and Stay Closed
3 = Continuous Pulse on & off
25 has not
( 1 sec ON, 1 sec OFF)