First Alert FA142C Installation Instructions Manual page 90

Security systems
Hide thumbs Also See for FA142C:
Table of Contents

Advertisement

1. This is a "Grade A" residential system.
2. The 4285 Phone module and 7720PLUS or 7820 Long Range Radios have not been UL
tested and cannot, therefore, be used in a UL installation.
3. The Entry Delay (field 38) cannot be greater than 45 seconds (set to 3 or less) for UL
installations.
4. The maximum number of reports per armed period (field 92) must be unlimited (set to 1)
for UL installations.
5. Periodic testing (field 49) must be at least every 24 hours (set to 1) for UL installations.
6. Alarm Sounder plus Auxiliary Power currents must not exceed 600mA total for UL
installations.
7. Downloading is not permissible for UL installations.
CALIFORNIA STATE FIRE MARSHAL (CSFM)
24 HOUR BATTERY BACK-UP REQUIREMENTS
The California State Fire Marshal has published new regulations which require that all residential fire alarm
control panels installed after June 30, 1993 must be provided with a back-up battery which has sufficient
capacity to operate the panel and its attached peripheral devices for 24 hours in the intended standby
condition, followed by at least 4 minutes in the intended fire alarm signaling condition.
This control panel can meet these requirements without using a supplementary power supply, provided that
the panel's auxiliary power and bell output currents are limited as indicated below.
OUTPUT LIMITATIONS TO MEET CSFM 24 HOUR BATTERY BACK-UP REQUIREMENTS
OUTPUT CURRENT LIMITATIONS
OUTPUT CURRENT
TOTAL
600mA maximum total
of
auxiliary power
plus bell output currents.
‡ Note: Use two batteries, connected in parallel. Obtain an Ademco No. 4100EOLR Resistor Kit. A dual battery
harness is provided with the kit. The kit also contains EOL resistors with spade lug/heat shrink tubing
construction which has been approved by UL and CSFM for fire zone usage. Both batteries will fit inside the
panel's cabinet.
UL NOTICES
FOR UL LISTED RESIDENTIAL FIRE INSTALLATIONS
MAXIMUM
AUXILIARY CURRENT
45mA
160mA
200mA
425mA
BATTERY INFORMATION
BATTERY CAPACITY
TO USE (Amp/Hrs)
4AH
7AH
8AH
14AH
– 90 –
RECOMMENDED BATTERY
(Yuasa Model No.)
NP4-12
NP7-12
NP4-12 (two) ‡
NP7-12 (two) ‡

Hide quick links: