Fujitsu Airstage V series Service Manual page 8

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V series:
Table of Contents

Advertisement

Section
check item
Pipe heat insulating
Others
material
Drain
Indoor unit
hose
Section
check item
Wiring
Power supply cable
Breaker
Transmission cable
Terminal resistor
Remote controller cable
Section
check item
System
Address
Refrigeration circuit Set all the address. And avoid overlapping.
setting
Indoor unit
Outdoor unit
Remote controller
Others
Outdoor unit
capacity
Number of
slave unit
Pipe length
Refrigerant type
Connected
outdoor unit
System
distribution diagram
Description
Use the Pipe heat insulating material
as per specifications.
Drain water does not collects in the middle of drain hose.
Install the drain hose with downward
gradient (1/50 to 2/50) and so there are no rises or
traps in the hose.
Description
Use the power supply cable as per specifications.
There are not deficient phase, miss wiring, and breaking
of wire for each indoor unit and outdoor unit.
Use the ground wire as per specifications.
There are not miss wiring, and breaking of wire.
Use the breaker as per specifications.
Use the transmission cable as per specifications.
There are not miss wiring, and breaking of wire
for each indoor unit and outdoor unit.
The wiring length is within the limits of specifications.
Use the ground wire as per specifications.
There are not miss wiring, and breaking of wire.
Use the terminal resistor that came with the master unit.
Use the remote controller cable as per specifications.
Connect the remote controller cable correctly.
Description
Check current setting. If the setting is wrong,
set the DIP SW as per specifications. (For outdoor unit)
Check current setting. If the setting is wrong,
set the DIP SW as per specifications. (For outdoor unit)
Check current setting. If the setting is wrong,
set the DIP SW as per specifications. (For outdoor unit)
Check current setting. If the setting is wrong,
set the DIP SW as per specifications. (For indoor unit)
Check current setting. If the setting is wrong,
set the DIP SW as per specifications. (For indoor unit)
System distribution diagram (Piping distribution diagram,
Wiring distribution diagram and
Address distribution diagram) shall be always updated.
01-02
DESIGN&TECHNICAL DATA
6-2-5 SELECTION OF PIPE HEAT
INSULATIONG MATERIAL
INSTALLATION MANUAL
6. INSTALLING DRAIN HOSE
5. INSTALLING DRAIN HOSE (Duct Type)
1. INDOOR UNIT INSTALLATION
DESIGN&TECHNICAL DATA
6-3-2 POWER SUPPLY CABLE WIRING
3-10 ELECTRIC CHARACTERISTICS
4-4 ELECTRIC CHARACTERISTICS
INSTALLATION MANUAL
8 ELECTRICAL WIRING (Compact Duct Type)
7 ELECTRICAL WIRING (Duct Type)
6 ELECTRICAL WIRING (Wall Mounted Type)
5 OUTDOOR UNIT WIRING SETTING
DESIGN&TECHNICAL DATA
6-3-2 POWER SUPPLY CABLE WIRING
3-10 ELECTRIC CHARACTERISTICS
DESIGN&TECHNICAL DATA
6-3-3 TRANSMISSON LINE
INSTALLATION MANUAL
8 ELECTRICAL WIRING (Compact Duct Type)
7 ELECTRICAL WIRING (Duct Type)
6 ELECTRICAL WIRING (Wall Mounted Type)
5 OUTDOOR UNIT WIRING SETTING
INSTALLATION MANUAL
6-5 TERMINAL RESISTOR SETTING
DESIGN&TECHNICAL DATA
6-3-1 WIRING SPECIFICATION
INSTALLATION MANUAL
8 ELECTRICAL WIRING (Compact Duct Type)
7 ELECTRICAL WIRING (Duct Type)
6 ELECTRICAL WIRING (Wall Mounted Type)
DESIGN&TECHNICAL DATA
6-4-2 ADDRESS SETTING
DESIGN&TECHNICAL DATA
6-6-2 SWITCH FUNCTION
(Only for master unit)
(Only for master unit)
DESIGN&TECHNICAL DATA
6-6-2/6-6-6 SWITCH FUNCTION
Check
Standard
field
(Compact Duct Type)
(Wall Mounted Type)
Check
Standard
field
Check
Standard
field