Troubleshooting 23 - Outdoor Unit Error Method: Discharge Temp. Sensor 2 Error - Fujitsu Airstage V series Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V series:
Table of Contents

Advertisement

Trouble shooting 23
OUTDOOR UNIT Error Method:
Discharge Temp. Sensor 2 Error
Detective Actuators:
Outdoor Unit Controller PCB circuit
Discharge Thermistor
Forecast of Cause : 1. Connector connection failure 2. Thermistor failure 3. Controller PCB failure
Check Point 1 : Check connection of Connector
p Check if connector is loose or removed
p Check erroneous connection
p Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
OK
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
Temperature (°C)
Resistance Value (
)
Temperature (°C)
Resistance Value (
)
If Thermistor is either open or shorted, replace it and reset the power.
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Outdoor Unit Schematic(CN27)
Suction Gas Temp. Thermistor(CN27:1-2)
Outdoor Temp. Thermistor(CN27:3-4)
Discharge Thermistor 1 (CN27:5-6)
Discharge Thermistor 2 (CN27:7-8)
Discharge Thermistor 3 (CN27:9-10)
If the voltage does not appear, replace Controller PCB and reset the original address.
Indicate or Display:
Outdoor Unit : LED1 Flash, LED3
Indoor Unit : Operation LED Lighted Continuously (Normal Operation)
ERROR CODE : E : 00
Detective details:
Discharge thermistor of Compressor 2 is shorted.
Discharge thermistor of Compressor 2 is open after 5 minutes of operation.
0
5
10
176
135
105
80
90
100
6.3
4.6
3.4
2 Time Blink
(No error display)
15
20
30
81.8
64.5
41.1
120
140
160
2.0
1.2
0.8
DC
06-34
40
50
60
26.9
18.1
12.5
180
0.5
70
8.8