"Cool" Position; "Heat" Position; "Fan" Position - Fujitsu Airstage V series Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V series:
Table of Contents

Advertisement

5-2-3 "COOL" Position

When using the cooling mode, set the temperature to a value lower than the current room
the indoor unit will not start the cooling operation and only the fan will rotate.
An example for COOLING TEMPERATURE CONTROL time chart (Manual setting)
Ts + 0.5 C
• Temperature
Ts
Ts - 0.5 C
3Min.
• Refrigerant
ON
OFF
flow
100%
• Opening of
0%
EEV
ON
• Indoor fan
OFF
Ts : Corrected setting temperature
T
R

5-2-4 "HEAT" POSITION

(1) When using the heating mode, set the temperature to a value higher than the current room
the indoor unit will not start the heating operation.
(2) After the start of heating operation, the fan of indoor unit will not rotate until the heater exchange is warmed up to
blow out warm air.
(3)
During defrosting, the OPERATION indicator lamp flashes 3 sec. ON and 1 sec. OFF, and repeat. The heating operation
will be temporarily interrupted.
An example for HEATING TEMPERATURE CONTROL time chart (Manual setting)
Ts + 0.5 C
• Temperature
Ts
Ts - 0.5 C
• Refrigerant
ON
OFF
flow
100%
• Opening of
0%
EEV
ON
• Indoor fan
OFF
Ts : Corrected setting temperature
T
R

5-2-4 "FAN" Position

(1) In this position, the fan merely rotates to circulate air, so the room temperature will not change.
(2) The fan will rotate at a fan speed set with the FAN CONTROL button.
(3) When only the "FAN" mode is being used, setting the fan speed at "AUTO" is equivalent to setting it at "LOW".
: Corrected room temperature
4Min. 1Min.
: Corrected room temperature
: Duration of cold air prevention
T
Ts + 0.5 C
: The thres hold temperature of start of refrigrant flow
Ts - 0.5 C
: The thres hold temperature of stop of refrigrant flow
4Min. 1Min.
Ts + 0.5 C
: The thres hold temperature of start of refrigrant flow
Ts - 0.5 C
: The thres hold temperature of stop of refrigrant flow
05-03
temperature, otherwise
R
temperature, otherwise
T
R
4Min. 1Min.

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents