Test Run From Outdoor Pc Board; Test Run From Remote Controller; Standard Wired Remote Controller; Standard Wireless Remote Controller - Fujitsu Airstage V series Service Manual

Multi air conditioning system for buildings
Hide thumbs Also See for Airstage V series:
Table of Contents

Advertisement

1-2-2 Test Run From Outdoor PC Board

All the indoor units connected to the outdoor unit can be test-operated by DIP switch setting. (Only for master unit)
SW1-1
OFF
ON
OFF
ON

1-2-3 Test Run From Remote Controller

1. Standard wired remote controller

Stop the indoor unit. Push the
button simultaneously for more than two seconds.
The air conditioner will start to conduct a test run and "
the remote controller display.
However, the
,
setting button does not have function,
but all other buttons, displays, and protection functions will operate.
Perform the test operation for 60 minutes.
To stop test run, push the
controller.
For the operation method, refer to the operating manual and perform operation
check.
Check that there are no abnormal sounds or vibration sounds during test run
operation.

2. Standard wireless remote controller

Short two metal contacts under the battery compartment lid, while the air conditioner is running.
To stop test run operation, push
remote controller.
When the air conditioner is being test run, the OPERATION
and TIMER lamps of indoor unit flash slowly at the same time.
SW1-2
Test Run
OFF
Normal operation
OFF
Cooling test run
Heating test run
ON
ON
Normal operation
button and
button of the standard wired remote
button of the wireless
Remarks
SW1-1/SW1-2:
OFF/ON or ON/OFF
SW1-1/SW1-2:
OFF/OFF or ON/ON
SW1-1/SW1-2:
OFF/OFF or ON/ON
SW1-1/SW1-2:
OFF/ON or ON/OFF
" will display on
01-04
OFF/OFF
ON/OFF
OFF/ON
ON/ON
UTB-YUB / GUB / TUB
DAY
DAY OFF
CLOCK ADJUST
ENERGY
THERMO
SET BACK
SAVE
SENSOR
DELETE
SET
UTB - YVB / GVB
START/STOP
button
Test run button
(Metal contacts)
TEST
RUN

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents