OUTPUT
CONNECTOR
OUTPUT VOLTAGE
12V
CN8
(WHITE)
0V
Output voltage : Hi DC12V + 2V
Lo
Permissible current : 15mA
Operation display
The output for CN8 is ON when the indoor unit is operating.
The output is off when the unit is stopped.
Indoor
Operation
unit
Stop
CN 8
12V
OUTPUT
0V
PARTS
Following cord (service parts) is required. Please use the parts number shown below
to order the cord from your sales representative.
Usage
Name and shapes
EXTERNAL
For output port
INPUT WIRE
For control
EXTERNAL
input port
INPUT WIRE
If the external indicator has malfunction, due to noise
please insert a ceramic capacitor (0.1 F 25V or more)
near the input port of the equipment.
STATUS
Operation
Stop
0V
Q'ty
1
1
02-39
Operation
Indicator
Parts No.
9368778002
9368779009
Operation
Indicator
+
1
CN 8
2
(WHITE)
-
+
1
2
-