Check Point : ARXA36 / 45LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
(150°C)
Check Point : ARXC36LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
(150°C)
Check Point : ARXC45 / 60LATF
p Check each winding resistance of the motor
If Resistance value is abnormal, replace motor.
Thermal protector
(
°C)
Super low(Blue)
Low(Violet)
Med(Pink)
Hi(Red)
(Black)
(AC)
(White)
Low(Blue)
Med(Violet)
Hi(Red)
(Black)
(AC)
(White)
Low(Blue)
Int.1(Violet)
Hi(Red)
(Black)
(AC)
(White)
06-103
Read Wire
Resistance value(20°C)
White - Red
Red
- Black
Red
- Pink
Pink - Violet
Violet - Blue
Read Wire
Resistance value(20°C)
White - Red
Red
- Black
Red
- Violet
Violet - Blue
Read Wire
Resistance value(20°C)
White - Red
Red
- Black
Red
- Violet
Violet - Blue
19.7 ± 8%
13.0 ± 8%
5.86 ± 8%
5.86 ± 8%
5.86 ± 8%
13.4 ± 8%
16.5 ± 8%
11.2 ± 8%
12.9 ± 8%
6.84 ± 8%
9.78 ± 8%
6.1 ± 8%
6.1 ± 8%