Mitsubishi SRK50ZHX-S Technical Manual page 57

Inverter wall mounted type room air-conditioner split system, air to air heat pump type
Table of Contents

Advertisement

(2) Identification
a) Piping set
A copper pipe as piping set for R410A must have a thickness as stated in Table 3 (see on page 50), and, as shown in Tables 5
and 6 (see on page 52), it also differs from R22 in flare processing and flare nut dimensions. So, it is necessary to choose a
piping set suitable for R410A.
b) Copper pipe with insulation
Before using a copper pipe with insulation, make sure that it has a thickness designated for R410A.
c) Bare copper pipe
It is necessary to use a bare copper pipe which has a thickness designated in Table 3 (see on page 50) and contains less
contaminants. As the bare copper pipe surface is naked, it is necessary to treat it with exceeding care and adopt a means for
identification to prevent improper usage by making it easily discriminable from other piping materials.
(3) Precautions before installation
Observe the following precautions when performing the piping connection at the site.
a) Keep any open ends of pipes be sealed with a cap, etc. until connected with the equipment.
b) Exercise great care when performing piping installation on a rainy day.
When water enters into the piping, the lubricating oil may deteriorate and cause the equipment to fail.
c) Carry out the piping connection in as short a time as possible.
If the piping is left open for a long period, fully purge the interior with nitrogen gas or dry it with a vacuum pump.
7.2.4 Brazing
(1) Processing the connected parts
As brazing is molten between the joined surfaces to yield high adhesive strength, it is necessary to secure a wide enough space to
be joined and also an adequate clearance between the joined surfaces. Copper pipe joints' minimum insertion depths, outer pipe
diameters and clearances between outer and inner pipe diameters are as shown in Table 10. In the case of bronze brazing filler,
when the clearance is about 0.05~0.1mm, the pipes can be connected most strongly.
Table 10. Copper pipe joints' minimum insertion depths and clearances
B
* When joining the pipes, either the pipe ends are processed, or pipes are connected by brazing with a socket joint.
(2) Brazing filler metal
a) Alloy brazing filler
An alloy mainly composed of silver and copper is used to join iron, copper or copper alloy. Although it excels in solderability,
it is relatively expensive.
b) Phosphor bronze brazing filler
Phosphor bronze brazing filler is generally used to join copper or copper alloy.
c) Low temperature solder
An alloy of tin and lead. An ordinary type of solder. Since it is weak in adhesive strength, it should not be used for refrigerant
pipe brazing.
* Cautions:
1) BCuP tends to react with sulphur and produce a fragile compound water solution, which may cause a gas leakage. So,
use any other type of brazing filler at a hot spring resort, etc., and coat the surface with a paint.
2) When performing brazing again at the time of servicing, use the same type of brazing filler.
Outer pipe diameter
D
(mm)
5~8
A
D
8~12
12~16
54
-
Minimum insertion depth
B
(mm)
6
7
8
-
Clearance
(A-D) × 1/2
(mm)
0.05~0.35
0.05~0.35
0.05~0.45

Advertisement

Table of Contents
loading

This manual is also suitable for:

Srk60zhx-s

Table of Contents