Note (1) The number of flashes when in the Service Mode do not include the 1.5 second period when the lights light up at first (starting signal). (See the example
shown below.)
ON
RUN light
(10's digit)
OFF
ON
TIMER light
(1's digit)
OFF
Notes
(2) Error display:
- Is not displayed. (automatic recovery only)
Displayed.
If there is a (
the number of times in (
If no (
Notes
(3) Auto Recovery:
- Does not occur
Auto recovery occurs.
(d) Remote control information tables
1) Operation switching
Display pattern when
in service mode
RUN light
(Operation switching)
0
1
2
3
4
* If no data are recorded (error code is normal), the information display in the remote control becomes as follows.
Remote control setting
Operation switching
Fan speed switching
(Example): Operation switching, fan speed switching, cooling HI
ON
RUN light
(10's digit)
OFF
ON
TIMER light
(1's digit)
OFF
• In the case of current cut (example: stop code "42")
The RUN light (10's digit) flashes 4 times and the TIMER light (1's digit) flashes 2 times.
4 × 10 + 2 × 1 = 42 → From the table, read the instructions for error code 42, "Current cut".
1.5 sec.
0.5 sec.
0.5 sec.
) displayed, the error display shows the number of times that an auto recovery occurred for the same reason has reached
).
) is displayed, the error display shows that the trouble has occurred once.