(7) Inspection procedures corresponding to detail of trouble
Sensor error
Is connector connection good?
YES
Is sensor resistance value good?
YES
Replace PCB.
◆ Discharge pipe sensor temperature characteristics
Temperature (˚C)
Resistance (kΩ)
0
5
10
15
20
25
30
35
40
45
50
55
60
65
Indoor fan motor error
Is connector connection good?
YES
* Disconnect the fan motor
connector, then investigate
the DC fan motor and indoor
unit circuit board separately.
Is the output of the indoor unit's
printed circuit board normal?
YES
Normal
NO
NO
Temperature (˚C)
Resistance (kΩ)
164
70
127
75
99
80
78
85
62
90
50
95
40
100
32
105
26
110
21
115
17
120
14
125
12
130
10
135
NO
Correct connector connection
Is DC fan motor resistance value good?
NO
Defective indoor PCB
Correct connection.
Replace sensor.
◆ Sensor temperature characteristics
8.7
7.3
6.2
5.3
(Broken wire)
4.5
3.9
3.3
2.9
2.5
2.2
1.9
(Shortcircuit)
1.6
1.4
1.3
YES
Replace indoor fan motor
Notes (1) See pages 45 for the DC fan motor and indoor unit circuit
(2) After making sure the DC fan motor and indoor unit circuit
41
-
-
[Broken sensor wire,
connector poor connection]
(Room temp., indoor unit heat exchanger
temp., outdoor unit heat exchanger
temp., outdoor air temp.)
3 0
2 5
2 0
1 5
1 0
5
1 0
0
1 0
2 0
3 0
Temperature (˚C)
[Defective fan motor, connector
poor connection, defective PCB]
NO
board check procedure.
board are normal, connect the connectors and confirm that
the fan motor is turning.
(If power is turned on while one or the other is broken down,
it could cause the other to break down also.)
4 0
5 0
6 0
7 0