17 TABLE OF STANDARD CONFIGURATIONS

No. of
config.
1107
Maximum current of the AC source
1108
Under voltage of the empty battery
1109
Sub-voltage of the charged battery
Restart voltage of the inverter after under voltage of the
1110
battery
1111
Automatic startup at power up
1112
Inverter frequency
1121
Maximum DC voltage for stopping the Xtender
1126
Source assistance (Smart Boost) permitted
1138
Battery charge current
Battery voltage correction according to the temperature
1139
1140
Battery maintenance voltage
1143
Voltage 1 to allow a new battery cycle
1144
Duration of under voltage 1 to allow a new cycle
1145
Voltage 2 to allow a new battery cycle
1146
Duration of under voltage 2 to allow a new cycle
1156
Battery absorption voltage
1157
Duration of absorption
1159
Current at end of absorption
1161
Minimum interval between absorptions
1187
Sensitivity of the charge detection (100% approx.25W)
1188
Number of pulse load reserach
1189
Time interval between load search pulses
1190
Duration of under voltage of battery before disconnection
1191
Dynamic compensation for under voltage
1194
Battery adaptive low voltage allowed
1195
Max voltage for adaptive low voltage
1198
Time elapsing before transfer relay opens
1199
ACin voltage causing the opening of the transfer relay
1200
Immediate open critical threshold for the transfer
Auxiliary contact 1 activated by voltage 1 {1247} after delays
1246
{1248}
1247
Voltage 1under which auxiliary contact 1 is activated
1248
Delays on voltage 1 to activate auxiliary contact 1
Auxiliary contact 1 activated by voltage 2 {1250} after delays
1249
{1251}
1250
Voltage 2 under which auxiliary contact 1 is activated
1251
Delays on voltage 2 to activate auxiliary contact 1
Auxiliary contact 1 activated by voltage 3 {1253} after delays
1252
{1254}
1253
Voltage 3 under which auxiliary contact 1 is activated
1254
Delays on voltage 3 to activate auxiliary contact 1
Voltage 1above which auxiliary contact 1 is deactivated
1255
after delays
1256
Delays on voltage {1255} to deactivate auxiliary contact 1
1258
Auxiliary contact 1 activated by power 1
1259
Power 1 above which auxiliary contact 1 is activated
1260
Duration of power 1 for activating auxiliary contact 1
The second value concerns the 120Vac ranges
2
40
Denomination / description
V.3.1.0
Fact.
Units
value
value
2
A
30
V/cell
1.93
V/cell
1.75
V/cell
2
y/n
no
Hz
50 / 60
V/cell
2.84
y/n
no
A
60
mV/°C/
-5
cell
V/cell
2.27
V/cell
2.1
min.
30
V/cell
1.93
sec.
180
V/cell
2.4
h
2
Adc
10
h
3
%
10
--
1
sec.
0.8
min.
3
y/n
yes
o/n
no
V/cell
2.08
sec.
8
Vac
180 / 90
Vac
100 / 50
y/n
yes
V/cell
1.95
min.
1
y/n
yes
V/cell
2
min.
10
y/n
yes
V/cell
2.05
min.
60
V/cell
2.25
min.
60
y/n
yes
%
120
min.
1