Connect Wiring; Figure 16 Corrosion Transmitter With Remote Probe - Honeywell XYR 6000 Quick Start Manual

Onewireless
Hide thumbs Also See for XYR 6000:
Table of Contents

Advertisement

3. Process insertion
3.4. Corrosion models

Connect wiring

Step
1
See Figure 16. Open the transmitter's rear end cap (opposite end from display).
2
Open the cable gland (on right side below antenna). (Cable gland must be ordered as an
option.)
3
Feed probe wiring through the cable gland and connect to terminal block. See Figure 16. See
page 31 for terminal connections.
4
Plug battery connector into batteries.
5
Close rear end cap and cable gland.
22

Figure 16 Corrosion transmitter with remote probe

OneWireless XYR 6000 Transmitters Quick Start Guide
Action
Revision 3
8/8/07