Prepare Boiler Location; Flooring And Foundation; Residential Garage Installation - Weil-McLain GOLD CGt Manual

Natural gas-fired water boiler with tankless heater
Hide thumbs Also See for GOLD CGt:
Table of Contents

Advertisement

GOLD CGt Gas-Fired Water Boiler — Boiler Manual
1c
Prepare boiler location — clearances
You must provide openings for combustion and
ventilation air, l
boiler front when the boiler is installed in any space
providing less clearance than the recommended service
clearances shown in Figure 1. These openings must be
located as shown in Figures 1 and 2 to provide proper
air flow around the boiler. Never install the boiler in a
space with clearances less than the minimum clearances
shown in Figure 2. For openings with louvers or grills,
increase the dimensions of the opening so the free area
(after deduction for grills or louvers) will be no less
than required in Figure 2. Failure to comply can result
in a fire hazard or damage to boiler components,
resulting in potential for severe personal injury, death
or substantial property damage and reduced boiler life.
See page 10 for combustion air opening requirements
for spaces larger than the service clearances in Figure 1.
Provide the following clearances:
1. Hot water pipes — at least ½" from combustible
materials.
2. Recommended service clearances — See
spaces providing more clearance than Figure 1, use
pages 10 and 11.
3. Minimum clearances for tight spaces — See

Flooring and foundation

Flooring
The CGt boiler is approved for installation on
combustible flooring, but must never be installed on
carpeting.
Foundation
Provide a solid brick or
foundation pad if any of the following is true:
floor can become flooded.
the boiler mounting area is not level.
The minimum foundation size is

Residential garage installation

Precautions
Take the following special precautions when installing
the boiler in a residential garage. If the boiler is located in
a residential garage, per ANSI Z223.1, paragraph 5.1.9:
Mount the boiler a minimum of
above the floor
burner and ignition devices will be no less than
18 inches above the floor.
Locate or
damaged by a moving vehicle.
Part Number 550-110-290/0501
ocated on the wall or door opposite the
Figure 1
Do not install boiler on carpeting even
if foundation is used. Fire can result,
causing severe personal injury, death
or substantial property damage.
minimum 2-inch thick
25" long x 18"
18 inches
of the garage to assure the
so it cannot be
protect the boiler
Figure 1 Recommended clearances for
service
. For
071002
.
Figure 2
Provide
(2) fresh air openings
from bottom located on wall next to boiler front.
Figure 2 Minimum clearances for tight spaces
2"
between
pipe and
combustibles
concrete
0"
wide.
Rear
Within 2"
from floor
071003
Provide
(2) fresh air
openings
— 0" from top
and 2" from bottom located
on wall next to boiler front.
Flush to ceiling
or as close as
possible
"
3 5
2"
— 0" from top and 2"
Flush to top
or as close as
possible
1 9
"
0"
Right
side
Each opening must have
minimum free area of
1
square inch per
1,000
Btuh
of CGt boiler input.
7