GOLD CGt Gas-Fired Water Boiler — Boiler Manual
3d
Venting — direct exhaust — vent starter
1. Select a vent pipe manufacturer and
obtain all vent components needed,
based on boiler location and venting
method.
2. You must use the vent starter made by
the vent pipe manufacturer. See
, page 15,
4
Vent system components
for part number of each component,
listed by vent manufacturer.
Use only the vent
starter of the same
manufacturer as the
vent components. Do
not mix components
from different sys-
tems. The vent system
could fail, causing flue
gas spillage, resulting
in severe personal in-
jury or death.
3. Follow all applicable national, state,
local or provincial codes when venting
the CGt boiler.
4. Connect vent starter to blower
housing outlet as shown in the
through
, right.
Figures 8
11
a. Do not mix components from
different vent manufacturers.
b. Maintain minimum 2" clearance
from combustible materials to
vent pipe.
c. Seal with sealant specified by vent
pipe manufacturer, using ³⁄₈" bead
(not required for FasNSeal™).
d. Tighten strap at band clamp screw
until strap is snug around blower
housing.
16
Figure 8 FasNSeal™ vent starter
Table
,
Blower outlet
Band clamp strap
Band clamp screw
Band clamp screw
Figure 10 Saf-T Vent® vent starter
Saf-T Vent® starter
³⁄₈" Sealant bead
Blower outlet
Band clamp strap
Band clamp screw
Figure 9 Z-Vent II vent starter
FasNSeal™ starter
³⁄₈" Sealant bead
Blower outlet
Band clamp strap
071009
Band clamp screw
Figure 11 StaR-34 vent starter
³⁄₈" Sealant bead
Blower outlet
Band clamp strap
Band clamp screw
071011
Feed
Tighten
position
position
Z-Vent II starter
(see detail above)
071010
StaR-34 starter
071012
Part Number 550-110-290/0501