Weil-McLain GOLD CGt Manual page 9

Natural gas-fired water boiler with tankless heater
Hide thumbs Also See for GOLD CGt:
Table of Contents

Advertisement

GOLD CGt Gas-Fired Water Boiler — Boiler Manual
1e
Prepare boiler location — contamination
Air contamination
Please review the following information on potential
combustion air contamination problems.
Table 1 Corrosive contaminants
Products to avoid
Spray cans containing chloro/fluorocarbons
Permanent wave solutions
Chlorinated waxes/cleaners
Chlorine-based swimming pool chemicals
Calcium chloride used for thawing
Sodium chloride used for water softening
Refrigerant leaks
Paint or varnish removers
Hydrochloric acid/muriatic acid
Cements and glues
Antistatic fabric softeners used in clothes dryers
Chlorine-type bleaches, detergents, and cleaning
solvents found in household laundry rooms
Adhesives used to fasten building products and
other similar products
Part Number 550-110-290/0501
If the boiler is installed in
any area likely to cause contamination
would contaminate the air cannot be removed, you must either remove products permanently
or isolate the boiler and provide outside combustion air. Contaminated combustion air will
damage the boiler, resulting in possible severe personal injury, death or substantial property
damage.
Refer to
for products and areas which may cause
Table 1
contaminated combustion air.
Areas likely to have contaminants
Dry cleaning/laundry areas and establishments
Swimming pools
Metal fabrication plants
Beauty shops
Refrigeration repair shops
Photo processing plants
Auto body shops
Plastic manufacturing plants
Furniture refinishing areas and establishments
New building construction
Remodeling areas
Garages with workshops
, or if products which
9

Advertisement

Table of Contents