10-2-3. Check Code List (Outdoor)
Sensor lamp part
Remote
controller
Block indication
indication
Operation Timer
Ready
Flash
¥
¥
¡
F04
ALT
Outdoor unit Discharge temp. sensor (TD) error
¥
¥
¡
F06
ALT
Outdoor unit Temp. sensor (TE, TS, TL) error
¥
¥
¡
F08
ALT
Outdoor unit Outside temp. sensor (TO) error
l
l
¥
H01
Outdoor unit Compressor break down
l
l
¥
H02
Outdoor unit Compressor lock
l
l
¥
H03
Outdoor unit Current detection circuit error
l
l
¥
H06
Outdoor unit Low pressure system error
¥
¡
¥
L29
SIM
Outdoor unit Other outdoor unit error
l
¥
¥
P03
ALT
Outdoor unit Discharge temp. error
l
Outdoor unit
¥
¥
P04
ALT
High pressure system error, Power supply voltage error
l
¥
¥
P22
ALT
Outdoor unit Outdoor fan error
l
¥
¥
P26
ALT
Outdoor unit Inverter Idc operation
l
¥
¥
P29
ALT
Outdoor unit Position detection error
l
l
No remote controller master unit
¥
E01
Remote controller communication error
l
l
¥
E02
Remote controller send error
l
l
Regular communication error between indoor and
¥
E03
remote controller
l
l
¥
E04
Indoor/Outdoor serial error
l
l
¥
E08
Duplicated indoor addresses
l
l
¥
E09
Duplicated main remote controllers
l
l
¥
E10
Communication error between CPU
l
l
Regular communication error between master and
¥
E18
follower indoor units
l
¥
¥
L03
SIM
Duplicated indoor master units
l
¥
¥
L07
SIM
There is group cable in individual indoor unit.
l
¥
¥
L08
SIM
Unset indoor group address
l
¥
¥
L09
SIM
Unset indoor capacity
¥
¡
¥
L30
SIM
Outside error input to indoor unit (Interlock)
¥
¡
¥
L31
SIM
Phase order error and others
l
¥
¥
P19
ALT
4-way valve inverse error
ALT (Alternate): Alternate flashing when there are two flashing LED
Representative defective position
Detection
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Outdoor
Remote
controller
Remote
controller
²
Remote
controller
²
²
²
Outdoor
Outdoor
²
When this warning was detected before group construction/address check finish at power supply was turned on, the mode shifts automatically to AUTO address setup mode.
Explanation of error contents
Open/Short of discharge temp. sensor was detected.
Open/Short of heat exchanger temp. sensor was detected.
Miswiring between TE sensor and TS sensor
Open/Short of outside temp. sensor was detected.
When reached min-Hz by current release control, short-circuited current (Idc) after
DC excitation was detected.
Compressor lock was detected.
Current detection circuit error
Ps pressure sensor error, low pressure protective operation.
1) Defective parts on outdoor P .C. board (MCU communication, EEPROM, TH sensor error)
2) When outdoor service P .C. board was used, model type selection was inappropriate.
3) Other error (Heat sink abnormal overheat, gas leak, 4-way valve inverse error) was detected.
Error was detected by discharge temp. release control.
When case thermostat worked, error was detected by high release control from indoor/
outdoor heat exchanger temp. sensor. Power supply voltage error
Error (Over-current, lock, etc.) was detected on outdoor fan drive circuit.
Short-circuited protective operation of compressor drive circuit element (G-Tr /IGBT) worked.
Position detection error of compressor motor was detected.
Signal was not received from indoor unit.
Main remote controller was not set. (including 2 remote controllers)
Signal cannot be sent to indoor unit.
Indoor
No communication from remote controller and network adapter
Indoor
Serial communication error between indoor and outdoor
Indoor
Same address as yours was detected.
In 2-remote controller control, both were set as master.
(Indoor master unit stops warning and follower unit continues operation.)
Indoor
MCU communication error between main motor and micro computer
Regular communication was impossible between master and follower indoor units.
Indoor
Communication between twin master (Main unit) and follower (sub unit) was impossible.
Indoor
There are multiple master units in a group.
Indoor
When even one group connection indoor unit exists in individual indoor unit
Indoor
Indoor address group was unset.
Indoor
Capacity of indoor unit was unset.
Indoor
Abnormal stop by CN80 outside error input
Phase order of 3-phases power supply is abnormal (Thermo-OFF operation continues.) and others.
Indoor
In heating operation, error was detected by temp. down of indoor heat exchanger or temp. up ofTE, TS.
¡
: Go on,
SIM (Simultaneous): Simultaneous flashing when there are two flashing LED
l
¥
: Flash,
: Go off
Automatic
Operation
reset
continuation
×
×
×
×
¡
¡
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
×
¡
¡
×
¡
×
×
¡
¡
×
×
×
×
×
×
×
×
×
×
×
×
¡
×