[F01 error]
Is connection of TCJ sensor connector
(Indoor P .C. board CN102) normal?
YES
Are characteristics of
TCJ sensor resistance value normal?
YES
Check indoor P .C. board.
Defect → Replace
[P26 error]
Is power voltage normal?
YES
Are connections of
cabling/connector normal?
YES
"14" error does not occur during operation when
3P connector of compressor is not connected ?
YES
Is compressor normal?
YES
Check IPDU.
Defect → Replace.
NO
NO
∗
NO
NO
NO
NO
– 104 –
Correct connection of connector.
Replace TCJ sensor.
∗
Refer to 10-2-6. Relational graph of
temperature sensor resistance value
and temperature Characteristics-2.
Improve the power supply line.
Check and correct circuit cables.
Correct connection of connector.
Check and correct reactor connection.
Replace IPDU.
Check defective rear short of compressor.
Defect → Replace