Toshiba RAV-SM1603AT-E Service Manual page 143

Split type
Hide thumbs Also See for RAV-SM1603AT-E:
Table of Contents

Advertisement

No.
Part name
1. Detachment
7
Replacement
of electric parts
1) Carry out works of 1 of 1 , 3 and 4 .
Electrolytic
2) Remove the lead wire connected to the terminal block.
condenser
3) Remove the connector connected to the noise filter.
4) Remove the lead wire connected to the noise filter.
5) Cut the bundling band which binds the upper lead of
6) Remove the fixing screws for the electric parts box (A).
7) Remove the noise filter.
8) Remove the lead wires connected to the electrolytic
9) Remove screw of the condenser mounting band.
10) Remove the electrolytic condenser.
11) Mount a new electrolytic condenser.
Procedure
(IPDU crossover wire)
(IPDU crossover wire)
(Fuse crossover wire, power supply crossover wire)
the fan motor/lead of reactor.
(BT2T Ø4 × 6, 7 pcs.)
condenser. (Hexagonal bolt Ø5 × 12, 2 pcs.)
(BT2T Ø4 × 6, 1 pc.)
– 143 –
Remarks
Electric parts box (A)
Terminal block
IPDU
IPDU
IPDU
crossover wire
crossover wire
crossover wire
Fuse
Power supply
crossover wire
crossover wire
Bundling band
Condenser
Condenser
Condenser
mounting band
mounting band
mounting band
Hexagonal bolt
Hexagonal bolt
Hexagonal bolt

Hide quick links: