Toshiba RAV-SM1603AT-E Service Manual page 118

Split type
Hide thumbs Also See for RAV-SM1603AT-E:
Table of Contents

Advertisement

DN
Item
01
Filter sign lighting time
03
Central control address
06
Heating suction temp. shift
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
In automatic cooling/heating, temp.
width of cool → heat, heat →
1E
cool mode selection control point
28
Automatic reset of power failure
2A
Selection of option / error input (CN70)
Selection of thermostat output
2b
ƒ
(T10
)
31
Fan (Single operation)
32
Sensor selection
Humidifier control
40
(+Drain pump control)
(This function is not provided.)
60
Timer setting (Wired remote controller)
C2
Current demand X% to outdoor unit
Existence of remote controller save
D0
function
∗ Restriction ratio setting for save operation (DN code No. [C2]) can be set/changed from the normal DN setup
(Detail DN setup).
Function selection item No. (DN) list
Contents
0000: None
0002: 2500H
0004: 10000H
0001: No.1 unit
to
0099: Undecided
0000: No shift
0002: +2°C
to
0000: (1-way air discharge cassette)
0001: (4-way air discharge cassette) to 0037
0000: Undecided
0001: No.1 unit
to
0001: No.1 unit
to
0000: Individual
0002: Follower unit in group
0000: 0 deg
to
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
0000: None
0000: Filter input
0002: Humidifier input
0000: Indoor thermostat ON
0001: ON receiving output of outdoor compressor
0000: Impossible
0000: Body TA sensor
0000: No control
0001: Humidifier + Vaporizing type (Pump ON)
0002: Humidifier + Supersonic type
(Pump ON when specified time elapsed)
0003: Humidifier + Natural drain type (Pump OFF)
0000: Operable
0050: 50%
to
0000: Invalid (Impossible)
– 118 –
0001: 150H
0003: 5000H
0005: Clogging sensor used
0064: No.64 unit
0001: +1°C
0010: +10°C
(Up to +6 is recommended.)
0001 to 0034
0030: No.30 unit
0064: No.64 unit
0001: Master unit in group
0010: 10 deg
0001: Provided
0001: Alarm input
(Air cleaner, etc.)
0001: Possible
0001: Remote controller sensor
0001: Operation prohibited
0100: 100%
0001: Valid (Possible)
At shipment from factory
According to type
0099: Undecided
0002: +2°C
(Floor type 0000: 0°C)
According to model type
According to capacity type
0099: Undecided
0099: Undecided
0099: Undecided
0003: 3 deg
(Ts±1.5)
0000: None
0002: Humidifier
0000: Thermostat ON
0000: Impossible
0000: Body sensor
0003: Humidifier ON
Pump OFF
0000: Operable
0075: 75%
0001: Valid (Possible)