c. The running state data of different air-conditioners can be queried by pressing "Previous" or
"Next" to select the address.

5) Running Mode Setting Page Display

Running Mode Setting Display only has one page. And display the selected mode, auxiliary
function and the selected operation state.

6) Installation

1. Adopt Electrical Switch Box
The diameter of Central Control Monitor wire must be suitable for its length.
Electrical wiring tube must be suitable for the wires.
Turn a screwdriver at the concave on bottom panel of the Central Control Monitor to remove
the cover.
NOTE
Never turn screws too tightly, otherwise the cover would be dented, or the Liquid Crystal
would be broken.
Do not cut wires when installing the cover of Central Control Monitor.
2. Installation
Terminals P, Q, E at the back of CCM are connected to the terminal P, Q, E of PC.
The CCM power connects 220V~ 50Hz power directly to the terminal L, N,
back of wire controller.
1)
The communication cable of CCM and power cable should not be placed in the same
electrical wire tube and the two tubes should have 300-500mm distance.
2)
The length of CCM communication cable should not exceed 1200m.
- 307 -