Powerup Test - Hitachi SJ2002 Series Quick Reference Manual

Hide thumbs Also See for SJ2002 Series:
Table of Contents

Advertisement

Powerup Test

The Powerup Test procedure uses minimal parameter settings to run the
motor. The procedure describes two alternative methods for commanding
the inverter: via the inverter keypad, or via the logic terminals.
• Check power input and motor output wiring (see page 8 diagram).
• If using logic terminals for testing, verify correct wiring on [PCS],
[FW], [H], [O], and [L] (bottom row) per the diagram on page 8.
• Reverse [RV] input wiring (defaults to terminal [2]) is optional.
Step
Description
1
Set speed command
source setting
2
Set Run FW command
source
3
Set Run REV command
source
4
Set motor base freq.
5
Set motor poles
(2 / 4 / 6 / 8)
6
Set keypad display to
monitor freq.
Perform safety check
7
8
Run Forward command
9
Increase speed
10
Decrease speed
11
Stop motor
12
Run Reverse command
(optional)
13
Stop motor
Via Keypad
A001 = 00
(keypad pot.)
A002 = 02
(Run key)
A003 = 60
H004 = 4 (default), change only if
your motor is different
Access D001, press Func. key, display
0.0
will show
Disconnect load from motor
Turn keypad pot.
to MIN position
Press Run key
Rotate keypad
pot. CW dir.
Rotate keypad
pot. CCW dir.
Press Stop key
12
Via Logic
Terminals
A001 = 01,
[H–O–L] input
A002 = 01,
[FW] input
C002 = 01,
[RV] input
Ensure voltage on
[O]—[L] termi-
nals= 0V
Turn ON the
[FW] terminal
Increase voltage
at [O]
Decrease voltage
at [O]
Turn OFF the
[FW] terminal
Turn ON the [RV]
terminal
Turn OFF the
[RV] terminal