Powerup Test

The Powerup Test procedure uses minimal parameter settings to run
the motor. The procedure describes two alternative methods for
commanding the inverter: via the inverter keypad, or via the logic
terminals.
• Check power input and motor output wiring (see page 4 diagram).
• If using logic terminals for testing, verify correct wiring on [P24],
[FW], [H], [O], and [L] (bottom row) per the diagram on page 4.
• Reverse [RV] input wiring (defaults to terminal [2]) is optional.
Step
1
Set speed command
source setting
2
Set Run FW command
source
3
Set Run REV command
source
4
Set motor base freq.
5
Set motor poles
(2 / 4 / 6 / 8)
6
Set keypad display to
monitor freq.
Perform safety check
7
8
Run Forward command
9
Increase speed
10
Decrease speed
11
Stop motor
12
Run Reverse command
(optional)
13
Stop motor
Description
Via Keypad
A_01 = 00
(keypad pot.)
A_02 = 02
(Run key)
A_03 = 60
H_04 = 4 (default), change only if
your motor is different
Access D_01, press Func key, display
0.0
will show
Disconnect load from motor
Turn keypad pot.
to MIN position
Press Run key
Rotate keypad
pot. CW dir.
Rotate keypad
pot. CCW dir.
Press Stop key
8
Via Logic
Terminals
A_01 = 01,
[H–O–L] input
A_02 = 01,
[FW] input
C_02 = 01,
[RV] input
Ensure voltage on
[O]—[L] termi-
nals= 0V
Turn ON the
[FW] terminal
Increase voltage
at [O]
Decrease voltage
at [O]
Turn OFF the
[FW] terminal
Turn ON the [RV]
terminal
Turn OFF the
[RV] terminal