6-2. Operation Data
<Cooling>
Temperature
No. of
condition (°C)
operating
units
Indoor Outdoor
1 unit
27/19
35/–
2 units
<Heating>
Temperature
No. of
condition (°C)
operating
units
Indoor Outdoor
1 unit
20/–
7/6
2 units
NOTES :
(1) Measure surface temperature of heat exchanger pipe around center of heat exchanger path U bent.
(Thermistor themometer)
(2) Connecting piping condition : 5 m x 2 units
Operating combination
Standard
(Unit)
pressure
P (MPa)
A
B
M13YKCV-E
0,7 to 0,9
M13YKV-E
M10YKCV-E
0,9 to 1,1
M10YKV-E
M13YKCV-E M10YKCV-E
0,8 to 1,0
M13YKV-E
M10YKV-E
M10YKCV-E M10YKCV-E
0,8 to 1,0
M10YKV-E
M10YKV-E
Operating combination
Standard
(Unit)
pressure
P (MPa)
A
B
M13YKV-E
3,5 to 3,7
M10YKV-E 3,3 to 3,5
M13YKV-E M10YKV-E 2,5 to 2,7
M10YKV-E M10YKV-E 2,5 to 2,7
– 24 –
Heat exchanger
Indoor Outdoor Compressor
pipe temp.
fan
mode
T1 (°C)
T2 (°C)
9 to 11 46 to 48
High
11 to 13 45 to 47
High
11 to 13 50 to 52
High
10 to 12 50 to 52
High
Heat exchanger
Indoor Outdoor Compressor
pipe temp.
fan
mode
T1 (°C)
T2 (°C)
53 to 55
0 to 2
High
48 to 50
0 to 2
High
41 to 43
–2 to 0
High
41 to 43
–2 to 0
High
fan
revolution
mode
(rps)
High
62
MED.
38
High
74
High
74
fan
revolution
mode
(rps)
High
79
MED.
63
High
97
High
97