7-2. Operation Data

<Cooling>
Tempeature
Model name
condition(°C)
Indoor
Outdoor
27/19
35/-
25PKVPG-ND
35PKVPG-ND
<Heating>
Tempeature
Model name
condition(°C)
Indoor
Outdoor
20/-
7/6
25PKVPG-ND
35PKVPG-ND
NOTES :
1. Measure surface temperature of heat exchanger pipe around center of heat exchaner path U bent.
(Thermistor themometer)
2. Connecting piping condition : 5 m
Standard
RAS-
pressure
P (MPa)
1.1 to 1.2
0.9 to 1.1
Standard
RAS-
pressure
P (MPa)
2.1 to 2.3
2.4 to 2.6
Heat exchanger
pipe temp.
T1 (°C)
T2 (°C)
14 to 16
39 to 41
12 to 14
41 to 43
Heat exchanger
pipe temp.
T1 (°C)
T2 (°C)
3 to 4
33 to 35
36 to 38
2 to 3
- 22 -
FILE NO. SVM-17050
Indoor
Outdoor
fan mode
fan mode
High
High
High
High
Indoor
Outdoor
fan mode
fan mode
High
High
High
High
Compressor
revolution
(rps)
27
37
Compressor
revolution
(rps)
36
42