cLeaRances

cLeaRances tO cOMBustIBLes
Follow these instructions carefully to ensure safe installation. Failure to
follow instructions exactly can create a fire hazard.
the appliance cannot be installed on a carpet, tile or other combustible
material other than wood flooring. If installed on carpet or vinyl flooring,
the appliance shall be installed on a metal, wood or noncombustible
material panel extending full width and depth of the appliance.
12" Max.
Depth
72" Minimum 
Ceiling
6" Min.
FP2128
Figure 4 -
Clearances from the mantel, ceiling, and side wall.
ManteL cLeaRances
nOte: the combustible area above the facing must not protrude more than 3/4" from the facing. If it
does, it is considered a mantel and must meet the mantel requirements listed in this manual.
FP2595
mantel clearances
20300293
2
1
/
" Max Depth
2
16" Min.
From Opening
10" min.
From Opening
Hearth
8" Min.
Noncombustible
Resolution Direct Vent Gas Fireplace
Wall
12"
6"
16"
2
12"
10"
Top of Fireplace
Opening
side View
FP2129
Fireplace Opening
top View
Figure 5 -
Mantel clearances
FP2129
mantel leg
Stud
Insulation
Board
Standoff
1
/
"
2
FP2235
FP2204
mantel clearances
1"
1
/
"
1
2
3
/
"
1
2
4
/
"
1
2
/
"
1
2
2
3"
45°
5"
6"
9