EXAMPLE
If total horizontal needs to be 8', then the minimum required
vertical is 6'.
H=8' (45° + 90° + 90°) = 14' (equivalent horizontal)
From the graph the required vertical is 6'.
Figure 31 - (DV(LT,TT)42)
31259-3-0114
EXAMPLES - VENT RUN
24"
24" MINIMUM
CLEARANCE TO
COMBUSTIBLES
EXAMPLE
If total horizontal needs to be 10', then the minimum required
vertical is 6'.
H=10' (90° + 90°) = 16' (equivalent horizontal)
From the graph the required vertical is 7'.
Figure 32- (DV(LT,TT)42)