Empire Comfort Systems DVLT series Installation Instructions And Owner's Manual page 13

Direct vent zero clearance gas fireplace
Table of Contents

Advertisement

Vent Pipe Clearance
Note: Maintain one inch of clearance around vertical vent pipe (after
the first 96" framing). See Figure 16.
For horizontal vent, maintain a minimum 1" clearance to the bottom
and sides of the vent, and 3" clearance to combustibles above the
vent pipe. See Figure 17.
Combustible Surround Installation
2 X 4 HEADERS
STANDOFFS
14" OF NON-COMUBSTIBLE
MATERIALSUPPLIED WITH
THE FIREPLACE
31259-3-0114
INSTALLATION (continued)
Figure 16
Figure 17
COMBUSTIBLE
SURROUND
FINISH WALL
NON-COMBUSTIBLE
MATERIAL
1/2" LIP AT TOP OF
FIREPLACE OPENING
Figure 18
Finishing
Finish the walls with the material of your choice. Figure 4 on page 8
shows the minimum vertical and corresponding maximum horizontal
dimensions of mantels or other combustible projections above the
top front edge of the fireplace.
Only non-combustible materials may be used to cover the metal
fireplace face. See Figure 3, Page 8.
If the joints between the finished wall and the fireplace surround
(top and sides) are sealed, a 300°F minimum sealant material
must be used. These joints are not required to be sealed. Only
non-combustible material (using 300°F minimum adhesive if
needed), can be applied as facing to the fireplace surround.
Vent Runs
In planning the installation for the fireplace, it is necessary to install
certain components before the appliance is completely positioned
and installed. These include the direct vent system, gas piping for
the appliance and the electrical wiring.
The appliance can be mounted on any of the following surfaces:
1. A flat, hard combustible surface.
2. A raised wooden platform.
3. Six supports. (Example: Six concrete masonry blocks.) These
supports must be positioned so they contact all four perimeter
edges on the bottom of the unit and under the center leg supports,
if allowed by code.
VERTICAL, 90° ELBOW WITH HORIZONTAL TERMINATION
3" (76 mm)
MINIMUM
CLEARANCE TO
COMBUSTIBLES
80-1/4" (2038 mm) DV(LT,TT) 42
62-1/4" (1581 mm) DV(LT,TT) 36
MINIMUM FROM BOTTOM
OF FIREPLACE
WARNING
VENT CAP/
THIMBLE
WALL FIRESTOP
Figure 19
Page 13