Configuring Battery Settings; Running Automatic Battery Tests; Configuring Automatic Battery Tests; Configuring Automatic Restart - IBM 1000 VA LCD Installation And Maintenance Manual

Lcd tower ups
Hide thumbs Also See for 1000 VA LCD:
Table of Contents

Advertisement

Configuring battery settings

This section describes configuring the uninterruptible power supply settings to run
automatic battery tests.

Running automatic battery tests

The automatic discharge test is enabled by default and runs during the transition
from Float to Rest mode. After the test is complete, the charge cycle restarts to
completely charge the batteries and then continues to Rest mode. The automatic
test runs approximately once every three months and does not run again until after
three more Float to Rest mode transitions. If a manual battery test is requested, the
automatic battery test timer is reset so that it does not run for the next three
months.
For an automatic battery test to run, make sure that the following requirements are
met:
v The Automatic Battery Tests setting is enabled. (See "Configuring automatic
v The batteries are fully charged.
v The uninterruptible power supply is in Normal mode with no active alarms.
v The load is greater than 10%.

Configuring automatic battery tests

To configure the automatic battery tests, complete the following steps:
1. From the main menu, press the down (
2. Press the down (
3. Press the down (
4. Press the OK button for 1 second to confirm.

Configuring automatic restart

The uninterruptible power supply automatically restarts if the utility power returns
after the output was shut off because of depleted batteries, a shutdown input signal,
or an automatic shutdown command.
You can set the load segment for the amount of time to delay the restart when utility
power returns by using the Automatic Start Delay setting (see Table 8 on page 24).
28
1000 VA and 1500 VA LCD Tower UPS: Installation and Maintenance Guide
battery tests.")
menu, and press the OK button.
) button to scroll to Automatic Battery Tests, and press the
OK button.
) button to select whether to enable or disable the automatic
battery test.
) button to scroll to the Configuration

Advertisement

Table of Contents
loading

This manual is also suitable for:

1500 va

Table of Contents