IBM 1500VA Manual

IBM 1500VA Manual

Lcd 2u rack uninterruptible power supply for ibm system x

Advertisement

®
IBM 1500VA LCD 2U Rack Uninterruptible Power
Supply for IBM System x
IBM System x at-a-glance guide
The IBM 1500VA LCD 2U Rack uninterruptible power supply (UPS) delivers 1000 watts of power in only
2U of rack space, providing smart energy management and the highest level of power protection that
today's IT infrastructures require. With an efficiency rating of 95% or greater, the UPS helps reduce
energy usage and cooling costs, improves energy management, and optimizes workload performance
and availability for IBM System x and BladeCenter server applications. This high-density UPS packs
more real power (watts) into a space-saving 2U of rack space to protect more equipment and leaves room
for expanding IT systems.
The IBM 1500VA LCD 2U Rack UPS is shown in Figure 1.
Figure 1. IBM 1500VA LCD 2U Rack UPS for IBM System x
Did You Know?
The IBM 1500VA UPS has a bright, easily customizable, and graphical LCD display that lets you
configure the device and displays important UPS status information in one of nine languages (English,
French, German, Spanish, Russian, Korean, Japanese, Simplified Chinese, and Traditional Chinese).
The UPS is exceptionally easy to manage and an ideal solution for standardization across the global
enterprise.
This UPS enhances system availability with Advanced Battery Management (ABM) technology, which
significantly extends battery service life, allows individual control of receptacle groups to maximize run
time for critical devices in the event of a prolonged power outage, and provides a real-time clock that
enables precise shutdown and power up of systems in a preferred sequence, and records specific
power-related occurrences for more accurate trending and data analyses.
The IBM 1500VA UPS integrates with IBM Systems Director Active Energy Manager to help improve
energy management.
IBM 1500VA LCD 2U Rack Uninterruptible Power Supply for IBM System x
1

Advertisement

Table of Contents
loading

Summary of Contents for IBM 1500VA

  • Page 1 Supply for IBM System x IBM System x at-a-glance guide The IBM 1500VA LCD 2U Rack uninterruptible power supply (UPS) delivers 1000 watts of power in only 2U of rack space, providing smart energy management and the highest level of power protection that today's IT infrastructures require.
  • Page 2: Part Number Information

    Selecting the right IBM UPS can help protect against these potentially costly incidents. Part number information Table 1 shows the orderable part numbers and feature codes for the IBM 1500VA UPS. Table 1. Ordering part numbers and feature codes Description...
  • Page 3 Brazil 10A/250V C13/ NBR 14136 (4.3 m) 81Y2387 Taiwan 10A/125V C13/CNS 10917 (4.3 m) 81Y2388 Taiwan 10A/250V C13/CNS 10917 (4.3 m) 81Y2389 Switzerland 10A/250V C13/SEV 1011 (4.3 m) 81Y2390 IBM 1500VA LCD 2U Rack Uninterruptible Power Supply for IBM System x...
  • Page 4 Features The IBM 1500VA LCD 2U Rack UPS includes the following features and capabilities: It has a high efficiency 1.5KVA UPS for increased rack power density.  It occupies only 2U of vertical rack space.  It has over 95% energy efficiency at 100% load.
  • Page 5: Specifications

    Valve Regulated Lead Acid (VRLA) – maintenance-free, sealed, leak-proof Optional External Battery Pack Typical recharge time 4 hours to 90% charge from a UPS/battery discharge of 50% rated load IBM 1500VA LCD 2U Rack Uninterruptible Power Supply for IBM System x...
  • Page 6: Physical Specifications

    1500 VA 1000 W Note: Battery backup times are approximate and may vary with equipment, configuration, battery age, and temperature. The IBM 1500VA LCD 2U Rack UPS does not support Extended Battery Modules (EBMs). Physical specifications Height: 84 mm (3.3 in) ...
  • Page 7: Operating Environment

    The IBM 1500VA LCD 2U Rack UPS has a three-year limited warranty. Supported rack installation The IBM 1500VA LCD 2U Rack UPS requires 2 U of rack space in one of the following rack cabinets: IBM 42U Enterprise rack ...
  • Page 8 UPS, including the optional Network Management Card’s firmware level and IP address, if installed. Configuration: Allows you to change up to 17 user settings with minimal navigation.  The buttons have the following functions: IBM 1500VA LCD 2U Rack Uninterruptible Power Supply for IBM System x...
  • Page 9: Rear Panel

    Rear panel Figure 3 shows the rear panel of the IBM 1500VA LCD 2U Rack UPS (100V/120V), 5395-1AX. Figure 3. Rear panel of the IBM 1500VA LCD 2U Rack UPS (100V/120V), 5395-1AX...
  • Page 10: Network Management Card

    Network Management Card The IBM 1500VA LCD 2U Rack UPS also comes equipped with a communication bay for the installation of an optional Network Management Card (46M4110). The Network Management Card provides convenient over the network UPS remote monitoring and management through a standard web browser.
  • Page 11 Has support for IPv6  Can be installed while the UPS is online maintaining the highest system availability  Figure 6 shows the Network Management Card UPS properties window. IBM 1500VA LCD 2U Rack Uninterruptible Power Supply for IBM System x...
  • Page 12 Figure 6. IBM LCD UPS Network Management Card (NMC) UPS properties window IBM 1500VA LCD 2U Rack Uninterruptible Power Supply for IBM System x...
  • Page 13 UPS shutdown occurs. Figure 7 shows normal operating using the IBM UPS Manager. The input voltage is 122V, which is within the acceptable range, and is shown in the left pane. The output voltage of the UPS is 121V and is also within the acceptable range.
  • Page 14 Figure 8 shows that the utility power supply has failed and that the UPS is now operating on battery. The UPS Manager software indicates that there is 10 minutes of battery time available based on the current load. Figure 8. IBM UPS Manager warning status window IBM 1500VA LCD 2U Rack Uninterruptible Power Supply for IBM System x...
  • Page 15 Figure 9 shows the event notification window where you can configure how you (and other users) want to be notified when certain events occur. Figure 9. Event Notification window IBM 1500VA LCD 2U Rack Uninterruptible Power Supply for IBM System x...
  • Page 16: Ibm Environmental Monitoring Probe

    Its temperature and humidity thresholds are easily set to trigger alarm notifications or shut down the  protected system. Its status can be monitored from the IBM Systems Director AEM or from the Network Management  Card web interface. It measures temperatures between 0 and 80°C (32 and 176°F) with an accuracy of ±1°C.
  • Page 17 AEM collects power information for each device attached to an IBM UPS, presenting a more complete view of energy usage within the data center. The IBM Systems Director Active Energy Manager (AEM) helps: Collect power information from each device attached to an IBM UPS, thus presenting a more ...
  • Page 18: Related Publications

    IBM US Product Announcement  http://ibm.com/common/ssi/cgi-bin/ssialias?infotype=dd&subtype=ca&&htmlfid=897/ENUS110-159 IBM System x UPS product page  http://www.ibm.com/systems/x/hardware/options/upsrack.html IBM 1500VA LCD 2U Rack Uninterruptible Power Supply Installation and Maintenance Guide  http://www.ibm.com/support/docview.wss?uid=psg1MIGR-5085198 Network Management Card User Guide  http://www.ibm.com/support/docview.wss?uid=psg1MIGR-5085199 IBM System x Configuration and Options Guide ...
  • Page 19 Web sites. The materials at those Web sites are not part of the materials for this IBM product and use of those Web sites is at your own risk.IBM may use or distribute any of the information you supply in any way it believes appropriate without incurring any obligation to you.
  • Page 20 Machines Corporation in the United States, other countries, or both. These and other IBM trademarked terms are US registered or common law trademarks owned by IBM at the time this information was published. Such trademarks may also be registered or common law trademarks in other countries. A current list of IBM trademarks is available on the Web at http://www.ibm.com/legal/copytrade.shtml...

This manual is also suitable for:

1500va lcd 2u rack ups