IBM 1500 VA LCD 2U Rack UPS Replacement Procedure

IBM 1500 VA LCD 2U Rack UPS Replacement Procedure

Internal battery
Hide thumbs Also See for 1500 VA LCD 2U Rack UPS:

Advertisement

Quick Links

1500 VA LCD 2U Rack UPS
2200 VA LCD 2U Rack UPS
3000 VA LCD 3U Rack UPS
Internal Battery
Replacement Procedure

Advertisement

loading

Summary of Contents for IBM 1500 VA LCD 2U Rack UPS

  • Page 1 1500 VA LCD 2U Rack UPS 2200 VA LCD 2U Rack UPS 3000 VA LCD 3U Rack UPS Internal Battery Replacement Procedure...
  • Page 3: Internal Battery Replacement Procedure

    Exchange only with the IBM-approved part. Recycle or discard the battery as instructed by local regulations. In the United States, IBM has a process for the collection of this battery. For information, call 1-800-426-4333. Have the IBM part number for the battery unit available when you call.
  • Page 4: Tools Required

    Tools required 1x #5 flat-head screwdriver Procedure To remove input power to change the battery, complete the following steps. Note: Qualified personnel can replace internal batteries without shutting down the uninterruptible power supply and without having to remove the uninterruptible power supply from the rack cabinet.
  • Page 5 2. Loosen the thumbscrew on the metal battery cover (this may require the #5 flat-head screwdriver), slide the cover to the right , and open the cover...
  • Page 6 3. Disconnect the internal battery connector and move connector on the battery out of the way and place the internal connector into the holder in the cover door...
  • Page 7 4. Using the plastic tabs, pull the battery module partially out of the bay , see graphics on previous page for more details. 5. See the following table to determine how many people are required to lift the internal battery module. Some battery modules might require two people to lift Battery description Weight Handling requirement...
  • Page 8 7. With two hands (four hands for a 3000 VA battery module), slide the new battery module into the uninterruptible power supply...
  • Page 9 8. Connect the internal battery connector - see graphics on previous page for more details - after pulling it out of the holder in the cover door with the connector on the battery. Note: A small amount of arcing might occur when you connect the batteries. This is normal and does not damage the unit or present any safety concern.
  • Page 10 10. To attach the uninterruptible power supply front bezel, press the two side latches toward each other, align the bezel with the uninterruptible power supply, and snap it into place.
  • Page 12 This document was compiled and written by Christian Flatscher © 2011 IBM Corp. © 2011 IBM UK Ltd.