Configuring Automatic On Battery Shutdown - IBM 1000 VA LCD Installation And Maintenance Manual

Lcd tower ups
Hide thumbs Also See for 1000 VA LCD:
Table of Contents

Advertisement

To set the restart delay times for each load segment, complete the following steps:
1. From the main menu, press the down (
2. Press the down (
3. Press the down (
4. Press the down (
5. Press the OK button for 1 second to confirm.
6. Repeat step 3 to step 5 to set the other load segment, if applicable.
Notes:
1. Load segment on/off commands that are issued through the Control menu
2. A single load segment delay applies to both receptacles. However, there is an

Configuring automatic on battery shutdown

You can use the Automatic on Battery Shutdown setting to configure how soon
the load segment shuts down when the uninterruptible power supply transfers to
Battery mode:
v If the Automatic on Battery Shutdown setting is set to Off (default), the load
v If the Automatic on Battery Shutdown setting is set to zero seconds (0s), the
v If you select a value, the load segment turns off automatically after the selected
To set the shutdown times for each load segment, complete the following steps:
1. From the main menu, press the down (
2. Press the down (
3. Press the down (
4. Press the down (
5. Press the OK button for 1 second to confirm.
6. Repeat step 3 to step 5 to set the other load segment, if applicable.
menu, and press the OK button.
) button to scroll to Automatic Start Delay, and press the
OK button.
) button to select the load segment that you want to set and
press the OK button.
) button to select the restart delay for the load segment.
You can specify one of the following options for the restart delay time for each
load segment:
v Select zero seconds to restart immediately.
v Select 1 - 32767 seconds to delay for the specified time.
v Select Off.
override the user settings for load segments.
additional automatic 1-second delay between closing segments 1 and 2. The
delay is always present when an On command is issued for both segments at
the same time.
segment turns off only when you manually press the button, issue an external
command, or turn it off through the display (Control > Load Segments).
load segment turns off automatically when the uninterruptible power supply on
Battery state is activated.
delay while the uninterruptible power supply operates on battery, but the
shutdown is canceled if the utility power returns before the delay has expired.
menu, and press the OK button.
) button to scroll to Automatic on Battery Shutdown, and
press the OK button.
) button to select the load segment that you want to set and
press the OK button.
) button to select the shutdown delay for the load segment.
) button to scroll to the Configuration
) button to scroll to the Configuration
Chapter 3. Operating the uninterruptible power supply
27