6.8.11 PID proportional band (network input config SNVT_count nciInvPIDPro)

You can set the proportional band of the PID control of the inverter.
To disable integral control, set "0.0%" or "6553.5".
Data Name
nciInvPIDPro
⋅ Data acceptance timing....At network variable receive when the inverter is at a stop (nv_update_occurs event)
Set the value 10 times greater than the desired value in nciInvPIDPro.
Example:
If you want to set 50.0%, set "500", the value 10 times greater than 50.0.
REMARKS
Refer to the inverter manual (applied) for use of PID control function.

6.8.12 PID integral time (network input config SNVT_time_sec nciInvPIDIntTm)

You can set the integral time of the PID control of the inverter.
To disable integral control, set "0.0s" or "6553.5".
Data Name
nciInvPIDIntTm
⋅ Data acceptance timing....At network variable receive when the inverter is at a stop (nv_update_occurs event)
REMARKS
Refer to the inverter manual (applied) for use of PID control function.
Initial Value
Initial value of Pr. 129
0.0% to 1000.0%, 6553.5
Initial Value
Initial value of Pr. 130
0.0s to 3600.0s, 6553.5
Range
Increments
0.1%/bit
Range
Increments
0.1s/bit
NETWORK VARIABLES
Setting Value
Storage Location
Pr.129
Setting Value
Storage Location
Pr.130