6.5.7
Output frequency monitor (0.005% increments) (network output
SNVT_lev_percent nvoInvOutFreqP)
You can monitor the output frequency of the inverter in 0.005% increments on the assumption that the
frequency set in "% set reference frequency (nciInvSetFreqBas) " is 100%. (Refer to page 73.)
Data Name
nvoInvOutFreqP
⋅ Data send event ...................... When data changes in 0.005% increments
⋅ Data send timing ..................... As set in Pr. 388 Heartbeat send time interval and Pr. 389 Minimum heartbeat
Example:
When inverter output frequency = 90.0Hz and % set reference frequency = 60.0Hz,
90.0Hz
= 1.5
60.0Hz
REMARKS
⋅ Monitoring is disabled at less than the minimum frequency resolution (0.01Hz) of the inverter.
⋅ This variable is similar to "output frequency monitor (0.1Hz increments)" but may sometimes differ from it in data
send timing since they are different in mutual resolution. (Refer to page 46.)
Initial Value
0.000%
send time. (Refer to page 75.)
Therefore, the monitoring value is 150.000%.
NETWORK VARIABLES
Range
0.000% to 163.830%
Increments
0.005%/bit
47