X609 Terminal Strip - Siemens SINAMICS S120 Manual

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components
2.6 Active Interface Modules
2.6.3.6

X609 terminal strip

Table 2- 26
X609 terminal strip
Termina
l
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Max. connectable cross-section 1.5 mm
* Series connection NO contact of precharge contactor and bypass contactor (only for frame size FI, GI)
NOTICE
Active Interface Modules in frame sizes HI and JI
Active Interface Modules of frame sizes HI and JI require a signal on terminal X609:11 and
12 to control the fans. If this signal is not present during operation, the fans do not rotate
and the module is shut down on overtemperature.
72
Designation
P24
P24
M
M
L
L
N
N
Precharge contactor–A1
Precharge contactor–A2
Bypass contactor–A1
Bypass contactor–A2
Contactor feedback 1 *
Contactor feedback 2 *
2
Technical specifications
Voltage: 24 VDC (20.4 ... 28.5 V)
Current consumption: Max. 0.25 A
Voltage: 230 VAC (195.5 ... 264.5 V)
Current consumption: Max. 10 A
Fan operating currents, see "Technical data"
Voltage: 230 VAC (195.5 ...
264.5 V)
Current consumption: Max.
4 A
Voltage: 230 VAC (195.5 ...
264.5 V)
Current consumption: Max.
6 A
Voltage: 230 VAC (195.5 ... 264.5 V)
Max. permissible current: 6 A
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
To Active Line Module, X9:5
To Active Line Module, X9:6
To Active Line Module, X9:3
To Active Line Module, X9:4
Chassis power units