3.4.3.3
Line/load connection
Table 3- 31
Line/load connection of the Active Line Module
Terminals
U1, V1, W1
3 AC power input
DCPA, DCNA
Connection for Braking
Module
DCP, DCN
DC power output
PE connection
PE1, PE2
) Dimensions for connecting alternative cable lugs, see "cable lugs" in the appendix.
1
Chassis power units
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
Technical specifications
Voltage:
3 AC 380 V -10 % (-15 % < 1 min) ... 3 AC 480 V +10 %
•
3 AC 500 V -10 % (-15 % < 1 min) ... 3 AC 690 V +10 %
•
Frequency: 47 ... 63 Hz
Connecting thread:
Frame sizes FX / GX: M10 / 25 Nm for cable lugs in accordance with DIN 46234 /
•
DIN 46235
1)
Frame sizes HX / JX: M12 / 50 Nm for cable lugs in accordance with DIN 46234 /
•
DIN 46235
1)
Voltage:
570 ... 720 V DC
•
750 ... 1035 V DC
•
Connections:
Frame sizes FX / GX: Threaded bolts M6 / 6 Nm for cable lugs in accordance with
•
DIN 46234 / DIN 46235
Frame sizes HX / JX: Connection for connection clip
•
Voltage:
570 ... 720 V DC
•
750 ... 1035 V DC
•
Connections:
Frame sizes FX / GX: Thread M10 / 25 Nm for cable lugs in accordance with DIN 46234 /
•
DIN 46235
1)
Frame sizes HX / JX: d = 12 mm (M12/50 Nm) flat connector for busbar
•
Connecting thread:
Frame sizes FX / GX: M10 / 25 Nm for cable lugs in accordance with DIN 46234 /
•
DIN 46235
1)
Frame sizes HX / JX: M12 / 50 Nm for cable lugs in accordance with DIN 46234 /
•
DIN 46235
1)
1)
Line Modules
3.4 Active Line Modules
157