Drive-Cliq Interface X500; X609 Terminal Strip - Siemens SINAMICS S120 Equipment Manual

Chassis power units
Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Line-side power components
2.5 Active Interface Modules
2.5.3.4

DRIVE-CLiQ interface X500

Table 2- 16
DRIVE-CLiQ interface X500
PIN
1
2
3
4
5
6
7
8
A
B
Blanking plate for DRIVE-CLiQ interface: Yamaichi, order no.: Y-ConAS-13
2.5.3.5

X609 terminal strip

Table 2- 17
X609 terminal strip
Terminal
1
2
3
4
5
6
7
8
9
10
11
12
13
14
Max. connectable cross-section 1.5 mm
* Series connection NO contact of precharging contactor and bridging contactor (only for frame size FI, GI)
60
Signal name
TXP
TXN
RXP
Reserved, do not use
Reserved, do not use
RXN
Reserved, do not use
Reserved, do not use
+ (24 V)
M (0 V)
Designation
P24
P24
M
M
L
L
N
N
Precharging contactor–A1
Precharging contactor–A2
Bridging contactor–A1
Bridging contactor–A2
Contactor feedback 1 *
Contactor feedback 2 *
2
Technical specifications
Transmit data +
Transmit data -
Receive data +
Receive data -
24 V power supply
Electronics ground
Technical specifications
Voltage: 24 V DC (20.4 V – 28.5 V)
Power consumption: max. 0.25 A
Voltage: 230 V AC (195.5 V – 264.5 V)
Power consumption: max. 10 A
Fan operating currents, see "Technical specifications"
Voltage: 230 V AC
(195.5 V – 264.5 V)
Power consumption: max. 4 A
Voltage: 230 V AC
(195.5 V – 264.5 V)
Power consumption: max. 6 A
Voltage: 230VAC (195.5V – 264.5V)
Max. permissible current: 6 A
Manual, (GH3), 10/2008, 6SL3097-2AE00-0BP3
To Active Line Module, X9:5
To Active Line Module, X9:6
To Active Line Module, X9:3
To Active Line Module, X9:4
Chassis power units

Advertisement

Table of Contents
loading

Table of Contents