3.2.3.3

Line/load connection

Table 3- 2
Line/load connection of the Basic Line Module
Terminals
U1, V1, W1
3 AC power input
DCPA, DCNA
Connection for Braking
Module
DCP, DCN
DC power output
PE connection
) Dimensions for connecting alternative cable lugs, see "cable lugs" in the appendix.
1
3.2.3.4

X9 terminal strip

Table 3- 3
Terminal strip X9 for Basic Line Modules, frame sizes FB, GB
Terminal
1
2
3
4
5
6
Max. connectable cross-section 1.5 mm
Chassis power units
Manual, (GH3), 01/2013, 6SL3097-4AE00-0BP3
Technical specifications
Voltage:
3 AC 380 V -10% (-15% < 1 min) ... 3 AC 480 V +10%
3 AC 500 V -10% (-15% < 1 min) ... 3 AC 690 V +10%
Frequency: 47 ... 63 Hz
Connecting thread:
Frame size FB: M10 / 25 Nm for cable lugs according to DIN 46234 / DIN 46235
Frame sizes GB, GD: M12 / 50 Nm for cable lugs according to DIN 46234 / DIN 46235
Voltage:
513 ... 648 VDC
675 ... 932 VDC
Connections:
Frame sizes FB, GB, GD: Threaded bolts M6 / 6 Nm for cable lugs according to DIN 46234 /
DIN 46235
1)
Voltage:
513 ... 648 VDC
675 ... 932 VDC
Connecting thread:
Frame size FB: M10 / 25 Nm for cable lugs according to DIN 46234 / DIN 46235
Frame sizes GB, GD: M12 / 50 Nm for cable lugs according to DIN 46234 / DIN 46235
Connecting thread:
Frame size FB: M10 / 25 Nm for cable lugs according to DIN 46234 / DIN 46235
Frame sizes GB, GD: M12 / 50 Nm for cable lugs according to DIN 46234 / DIN 46235
Signal name
P24V
M
Reserved, do not use
Line contactor control
2
Technical specifications
Voltage: 24 VDC (20.4 ... 28.8 V)
Current consumption: Max. 1.1 A
240 VAC: Max. 8 A
30 VDC: Max. 1 A
isolated
Line Modules
3.2 Basic Line Modules
1)
1)
1)
1)
1)
1)
95