Electrical Connections - Bryant 355BAV Installation, Start-Up, And Operating Instructions Manual

Direct-vent upflow variable-capacity condensing gas furnace
Hide thumbs Also See for 355BAV:
Table of Contents

Advertisement

Table 3 – Maximum Capacity of Pipe*
NOMINAL
INTERNAL
IRON PIPE
DIA.
SIZE
10
IN. (MM)
(3.0)
IN. (MM)
0.622
1/2 (13)
175
(158)
3/4 (19)
0.824 (21)
360
1 (25)
1.049 (27)
680
1-1/4 (32)
1.380 (35)
1400
1-1/2 (38)
1.610 (41)
2100
*Cubic ft of gas per hr for gas pressures of 0.5 psig (14 ---in. wc) or less, and
a pressure drop of 0.5 ---in. wc (based on a 0.60 specific gravity gas). Ref:
Table 9 ---2 NFPA 54 ---2002.
NOTE: The gas valve inlet pressure tap connection is suitable to
use as test gauge connection providing test pressure DOES NOT
exceed maximum 0.5 psig (14- -in. wc) stated on gas valve. (See
Fig. 51.)
Piping should be pressure and leak tested in accordance with
NFGC in the United States or NSCNGPIC in Canada, local, and
national plumbing and gas codes before the furnace has been
connected. If pressure exceeds 0.5 psig (14- -in. wc), gas supply
pipe must be disconnected from furnace and capped before
pressure test.
If test pressure is equal to or less than 0.5 psig (14- -in. wc), turn off
electric shutoff switch located on gas valve before test. It is
recommended that ground joint union be loosened before pressure
testing. After all connections have been made, purge lines and
check for leakage at furnace prior to placing it into service.
The gas supply pressure shall be within the maximum and
minimum inlet supply pressures marked on the rating plate with
the furnace burners ON at HI- -HEAT and OFF.

Electrical Connections

See Fig. 19 for field wiring diagram showing typical field 115- -v
and 24- -v wiring. Check all factory and field electrical connections
for tightness.
WARNING
!
ELECTRICAL SHOCK HAZARD
Failure to follow this warning could result in personal
injury or death.
Blower access door switch opens 115- -v power to
furnace control. No component operation can occur. Do
not bypass or close switch with panel removed.
LENGTH OF PIPE --- FT (M)
20
30
40
50
(6.0)
(9.1)
(12.1)
(15.2)
120
97
82
73
250
200
170
151
465
375
320
285
950
770
660
580
1460
1180
990
900
WARNING
!
UNIT MAY NOT OPERATE
Failure to follow this caution may result in intermittent
unit operation.
Furnace control must be grounded for proper operation
or control will lock out. Control is grounded through
green/yellow wire connected to gas valve and burner
box screw.
115- - v Wiring
Before proceeding with electrical connections, make certain that
voltage, frequency, and phase correspond to that specified on
furnace rating plate. Also, check to be sure that service provided by
power supply is sufficient to handle load imposed by this
equipment. Refer to rating plate or Table 4 for equipment electrical
specifications.
Make all electrical connections in accordance with National
Electrical Code (NEC) ANSI/NFPA 70- -2008 and any local codes
or ordinances that might apply. For Canadian installations, all
electrical connections must be made in accordance with Canadian
Electrical Code CSA C22.1 or authorities having jurisdiction.
Field- -supplied wiring shall conform with the limitations of 63_F
(33_C) rise.
The furnace must be electrically grounded in accordance with local
codes; or in the absence of local codes, with the National Electric
Code ANSI/NFPA 70 and/or the Canadian Electric Code, CSA
C22.1, Part I, if an external electrical source is utilized.
Use a separate branch electrical circuit containing a properly sized
fuse or circuit breaker for this furnace. See Table 4 for wire size
and fuse specifications. A disconnecting means must be located
within sight from and readily accessible to furnace.
NOTE: Proper polarity must be maintained for 115- -v wiring. If
polarity is incorrect or furnace is not grounded properly, furnace
control status code indicator light will flash rapidly and furnace
will NOT operate.
WARNING
!
FIRE HAZARD
Failure to follow this warning could result in intermittent
operation or performance satisfaction.
Do not connect aluminum wire between disconnect switch
and furnace. Use only copper wire. (See Fig. 20.)