Adjustments - Bryant 355BAV Installation, Start-Up, And Operating Instructions Manual

Direct-vent upflow variable-capacity condensing gas furnace
Hide thumbs Also See for 355BAV:
Table of Contents

Advertisement

CONTINUOUS BLOWER SPEED
SELECTION FROM THERMOSTAT
To select different continuous- -blower speeds from the room
thermostat, momentarily turn off the FAN switch or push button on
the room thermostat for 1- -3 seconds after the blower motor
BLWM is operating. The furnace control CPU will shift the
continuous- -blower airflow from the factory setting to the next
highest CF selection airflow as shown in Fig. 39. Momentarily
turning off the FAN switch again at the thermostat will shift the
continuous- -blower airflow up one more increment. If you repeat
this
procedure
enough,
you
continuous- -blower airflow to the lowest CF selection as shown in
Fig. 39. The selection can be changed as many times as desired and
is stored in the memory to be automatically used following a power
interruption.
This feature is disabled when blower off delay is set for 180 sec.
Heat Pump
See Fig. 45- -48 for thermostat connections.
When installed with a heat pump, the furnace control automatically
changes the timing sequence to avoid long blower off times during
demand defrost cycles. Whenever W/W1 is energized along with
Y1 or Y/Y2, the furnace control CPU will transition to or bring on
the blower motor BLWM at cooling airflow, low- -heat airflow, or
the midrange airflow, whichever is the lowest. The blower motor
BLWM will remain on until the main burners ignite, then shut OFF
and remain OFF for 25 seconds before coming back on at heating
airflow. When the W/W1 input signal disappears, the furnace
control begins a normal inducer post- -purge period while changing
the blower airflow. If Y/Y2 input is still energized, the furnace
control CPU will transition the blower motor BLWM airflow to
cooling airflow. If Y/Y2 input signal disappears and the Y1 input is
still energized, the furnace control CPU will transition the blower
motor BLWM to low- -cooling airflow. If both the Y1 and Y/Y2
signals disappear at the same time, the blower motor BLWM will
remain on at low- -heat airflow for the selected blower- -OFF delay
period. At the end of the blower- -OFF delay, the blower motor
BLWM will shut OFF unless G is still energized, in which case the
blower motor BLWM will operate at continuous blower airflow.
Component Test
The furnace features a component test system to help diagnose a
system problem in the case of a component failure. To initiate the
component test procedure, ensure that there are no thermostat
inputs to the control and all time delays have expired. Turn on
setup switch SW1- -6 (See Fig. 33.)
NOTE: The component test feature will not operate if the control
is receiving any thermostat signals or until all time delays have
expired.
The component test sequence is as follows:
1. The furnace control CPU turns the inducer motor IDM ON
at medium speed and keeps it ON through Step 3.
2. After waiting 15 seconds, the furnace control CPU turns the
hot surface igniter ON for 15 seconds, then OFF.
3. The furnace control CPU then turns the blower motor
BLWM ON at midrange airflow for 15 seconds, then OFF.
4. After shutting the blower motor BLWM OFF, the furnace
control CPU shuts the inducer motor IDM OFF.
NOTE: The EAC terminals are energized when the blower is
operating.
After the component test is completed, 1 or more status codes (11,
25, 41, or 42) will flash. See Service Label on blower access panel
or Service/Status Code Instructions for explanation of status codes.
NOTE: To repeat component test, turn setup switch SW1- -6 to
OFF and then back ON.
will
eventually
shift
the

ADJUSTMENTS

Set Gas Input Rate
Furnace gas input rate on rating plate is for installations at altitudes
up to 2000 ft. (610 M).
In the U.S.A., the input rating for altitudes above 2000 ft. (610 M)
must be reduced by 2 percent for each 1000 ft. (305 M) above sea
level.
In Canada, the input rating must be derated by 5 percent for
altitudes of 2000 - - 4500 ft. (610 - - 1372 M) above sea level.
Adjust manifold pressure to obtain input rate.
Furnace input rate must be within ¦2 percent of input rate on
furnace rating plate.
1. Determine natural gas orifice size and manifold pressure for
correct input.
a. Obtain average heat value (at installed altitude) from
local gas supplier.
b. Obtain average specific gravity from local gas supplier.
c. Verify furnace model. Table 11 can only be used for
model 355BAV Furnaces.
d. Find installation altitude in Table 11.
NOTE: For Canadian altitudes of 2000 - - 4500 ft. (610 - -1372 M),
use U.S.A. altitudes of 2001 to 3000 ft. (610 - - 914 M) in Table 11.
e. Find closest natural gas heat value and specific gravity
in Table 11.
f. Follow heat value and specific gravity lines to point of
intersection to find orifice size and low- - and high- -heat
manifold pressure settings for proper operation.
EXAMPLE: (0 - - 2000 ft. / 610 M altitude)
Heating value = 1050 Btu/cu ft
Specific gravity = 0.62
Therefore: Orifice No. 45
Manifold pressure: 3.8- -in. wc for high heat
* Furnace is shipped with No. 45 orifices. In this
example, all main burner orifices are the correct size and
do not need to be changed to obtain proper input rate.
g. Check and verify burner orifice size in furnace. NEVER
ASSUME ORIFICE SIZE; ALWAYS CHECK AND
VERIFY.
2. Adjust manifold pressure to obtain input rate.
a. Remove burner enclosure front.
NOTE: Manifold pressure MUST always be measured with the
burner box cover REMOVED.
b. Remove regulator seal caps that conceal adjustment
screws for low- - and high- -heat gas valve regulators.
(See Fig 51.)
c. Move setup switch SW1- -2 on control center to ON
position. (See Fig. 33.) This keeps furnace locked in
low- -heat operation.
d. Jumper R and W/W1 thermostat connections on control
to start furnace.
e. Turn low- -heat adjusting screw counterclockwise (out)
to decrease input rate or clockwise (in) to increase input
rate.
NOTE: DO NOT set low- -heat manifold pressure less than 1.3- -in.
wc or more than 1.7- -in. wc for natural gas. If manifold pressure is
outside this range, change main burner orifices to obtain manifold
pressure in this range.
44
1.6- -in. wc for low heat

Advertisement

Table of Contents
loading

Table of Contents