820SB/821SB: Installation, Start–Up, Operating and Service and Maintenance Instructions
Refer to
Table 5
for recommended gas pipe sizing. Risers must be used
to connect to furnace and to meter. Support all gas piping with
appropriate straps, hangers, etc. Use a minimum of 1 hanger every 6 ft.
(1.8 M). Joint compound (pipe dope) should be applied sparingly and
only to male threads of joints. Pipe dope must be resistant to the action
of propane gas.
Table 5 – Maximum Capacity of Pipe
Nominal:
1/2 (12.7) 3/4 (19.0)
Actual ID:
0.622
0.824
Length (ft)
Capacity in Cubic Feet of Gravity
172
360
10 (3.0)
118
247
20 (6.0)
95
199
30 (9.1)
81
170
40 (12.1)
72
151
50 (15.2)
NOTE: Cubic ft. of natural gas per hr for gas pressures of 0.5 psig
(14-in. w.c.) or less and a pressure drop of 0.5-in. w.c. (based on a 0.60
specific gravity gas). Ref: Chapter 6 current edition of NFPA 54/ANSI
Z223.1.
WARNING
!
FIRE OR EXPLOSION HAZARD
A failure to follow this warning could result in personal injury, death,
and/or property damage.
If local codes allow the use of a flexible gas appliance connector,
always use a new listed connector. Do not use a connector which has
previously served another gas appliance. Black iron pipe shall be
installed at the furnace gas control valve and extend a minimum of 2-in.
(51 mm) outside the furnace.
CAUTION
!
FURNACE DAMAGE HAZARD
Failure to follow this caution may result in furnace damage.
Connect gas pipe to furnace using a backup wrench to avoid damaging
gas controls and burner misalignment.
An accessible manual equipment shutoff valve MUST be installed
external to furnace casing and within 6 ft. (1.8 M) of furnace. A 1/8-in.
(3 mm) NPT plugged tapping, accessible for test gauge connection,
MUST be installed immediately upstream of gas supply connection to
furnace and downstream of manual equipment shutoff valve.
NOTE: The furnace gas control valve inlet pressure tap connection is
suitable to use as test gauge connection providing test pressure DOES
NOT exceed maximum 0.5 psig (14-in. w.c.) stated on gas control valve,
see
Fig.
21.
Fig. 21 – Redundant Automatic Gas Control Valve
Some installations require gas entry on right side of furnace (as viewed
in upflow), see
Fig.
22.
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
1 (25.4)
1-1/4 (31.8) 1-1/2 (38.1)
1.049
1.380
1.610
678
1390
2090
466
957
1430
374
768
1150
320
657
985
284
583
873
A06666
Fig. 22 – Burner and Manifold
Install a sediment trap in riser leading to furnace, see
capped nipple into lower end of tee. Capped nipple should extend below
level of furnace gas controls. Place a ground joint union between furnace
gas control valve and exterior manual equipment gas shutoff valve.
A 1/8-in. (3 mm) NPT plugged tapping, accessible for test gauge
connection, MUST be installed immediately upstream of gas supply
connection to furnace and downstream of manual equipment shutoff
valve.
Fig. 23 – Typical Gas Pipe Arrangement
Piping should be pressure and leak tested in accordance with the current
addition of the NFPA 54/ANSI Z223 in the United States, local, and
national plumbing and gas codes before the furnace has been connected.
After all connections have been made, purge lines and check for leakage
at furnace prior to operating furnace.
If pressure exceeds 0.5 psig (14-in. w.c.), gas supply pipe must be
disconnected from furnace and capped before and during supply pipe
pressure test. If test pressure is equal to or less than 0.5 psig (14-in. w.c.),
turn off electric shutoff switch located on furnace gas control valve and
accessible manual equipment shutoff valve before and during supply
pipe pressure test. After all connections have been made, purge lines and
check for leakage at furnace prior to operating furnace.
The gas supply pressure shall be within the maximum and minimum
inlet supply pressures marked on the rating plate with the furnace
burners ON and OFF.

ELECTRICAL CONNECTIONS

See
Fig. 24
for field wiring diagram showing typical field 115-V wiring.
Check all factory and field electrical connections for tightness.
Field-supplied wiring shall conform with the limitations of 63°F (33°C)
rise.
14
A08551