Bryant 355BAV Installation, Start-Up, And Operating Instructions Manual
Bryant 355BAV Installation, Start-Up, And Operating Instructions Manual

Bryant 355BAV Installation, Start-Up, And Operating Instructions Manual

Direct-vent upflow variable-capacity condensing gas furnace
Hide thumbs Also See for 355BAV:

Advertisement

355BAV
Direct- - Vent Upflow
Variable- -Capacity Condensing Gas Furnace
For Sizes 060- - 120, Series C
Visit www.Bryant.com
NOTE: Read the entire instruction manual before starting the installation.
NOTE: This furnace can be installed as a
NOTE: Special Venting Requirements for Installations in Canada
Installation in Canada must conform to the requirements of CSA
B149 code. Vent systems must be composed of pipe, fittings,
cements, and primers listed to ULC S636. The special vent fittings
and accessory concentric vent termination kits and accessory
external drain trap have been certified to ULC S636 for use with
those IPEX PVC vent components which have been certified to
this standard. In Canada, the primer and cement must be of the
same manufacturer as the vent system - - IPEX System 636,
PVC/CPVC Primer, Purple Violet for Flue Gas Venting and IPEX
System 636
t, PVC Cement for Flue Gas Venting, rated Class
(1)
IIA, 65 deg C. must be used with this venting system - - do not mix
primers and cements from one manufacturer with a vent system
from a different manufacturer.
instructions in the use of primer and cement and never use primer
or cement beyond its expiration date.
The safe operation, as defined by ULC S636, of the vent system is
based on following these installation instructions, the vent system
manufacturer's installation instructions, and proper use of primer
and cement. All fire stop and roof flashing used with this system
must be UL listed material. Acceptability under Canadian standard
CSA B149 is dependent upon full compliance with all installation
instructions. Under this standard, it is recommended that the vent
system be checked once a year by qualified service personnel.
The authority having jurisdiction (gas inspection authority,
municipal building department, fire department, etc) should be
consulted before installation to determine the need to obtain a
permit.
(1) System 636 is a trademark of IPEX Inc.
Installation, Start- -Up and

Operating Instructions

(2-pipe) direct vent or as an optional ventilated combustion air
Follow the manufacturer's
Consignes spéciales pour l'installation de ventillation au Canada
L'installation faite au Canada doit se conformer aux exigences du
code CSA B149. Ce systême de ventillation doit se composer de
tuyaux, raccords, ciments et apprêts conformes au ULC S636. La
tuyauterie de ventillation des gaz, ses accessoires, le terminal
concentrique mural ainsi que l'ensemble du drain de condensat
extérieur ont été certifiés ULCS 636 pour l'application des
composantes IPEX PVC qui sont certifiées à ce standard. Au
Canada l'apprêt et le ciment doivent être du même manufacturier
que le systême de ventillation - - IPEX Système 636, Apprêt
PVC/CPVC. Mauve Violette pour conduit en évacuation des gaz et
IPEX Système 636
t, ciment pour PVC pour conduit en
(1)
évacuation des gaz, évalué CLASSE IIA, 65 deg. C. doit ëtre
utilisé avec ce systèeme d'évacuation - - ne pas mélanger l'apprêt et
le ciment d'un manufacturier avec le systême de ventillation d'un
autre manufacturier. Bien suivre les indications du manufacturier
lors de l'utilisation de l'apprêt et du ciment et ne pas utiliser
ceux- -ci si la date d'expiration est atteinte.
L'opération sécuritaire, tel que définit par ULC S636, du système
de ventilation est basé sur les instructions d'installation suivantes,
ainsi que l'usage approprié de l'apprêt et ciment. Tout arrët feu et
solin de toit utilisés avec ce système doivent être des matériaux
listés UL. L'acceptation du standard Canadien CSA B419 est
directement relié à l'installation conforme aux instructions ci- - haut
mentionnées. Le standard Canadien recommande l' inspection par
un personel qualifié et ce, une fois par année.
Les autoritées ayant juridiction (inspecteurs de gas, inspecteurs en
bâtiments, département des incendies, etc) devraient être consultées
avant l'installation afin de déterminer si un permis est requis.
application.

Advertisement

Table of Contents
loading

Summary of Contents for Bryant 355BAV

  • Page 1: Operating Instructions

    355BAV Direct- - Vent Upflow Variable- -Capacity Condensing Gas Furnace For Sizes 060- - 120, Series C Installation, Start- -Up and Operating Instructions Visit www.Bryant.com NOTE: Read the entire instruction manual before starting the installation. (2-pipe) direct vent or as an optional ventilated combustion air NOTE: This furnace can be installed as a application.
  • Page 2: Table Of Contents

    ........As an ENERGY STAR® Partner, Bryant Corporation has deter- General .
  • Page 3: Required Notice For Massachusetts Installations

    Required Notice for Massachusetts Installations IMPORTANT The Commonwealth of Massachusetts requires compliance with regulation 248 CMR as follows: 5.08: Modifications to NFPA- -54, Chapter 10 2) Revise 10.8.3 by adding the following additional requirements: a. For all side wall horizontally vented gas fueled equipment installed in every dwelling, building or structure used in whole or in part for residential purposes, including those owned or operated by the Commonwealth and where the side wall exhaust vent termination is less than seven (7) feet above finished grade in the area of the venting, including but not limited to decks and porches, the following requirements shall be satisfied:...
  • Page 4: Safety Considerations

    FIRE, EXPLOSION, ELECTRICAL SHOCK AND CARBON MONOXIDE POISONING HAZARD The 355BAV Condensing Gas- -Fired Furnaces are CSA (formerly Failure to follow this warning could result in electrical shock, AGA and CGA) design- -certified for natural and propane gases fire, personal injury, or death.
  • Page 5: Dimensional Drawing

    ⁄ " (684 mm) (724 mm) ⁄ " ⁄ (667 mm) " ⁄ " (684 mm) AIRFL OW ⁄ (667 mm) ⁄ " (622 mm) " (14 mm) (567 mm) ⁄ " ⁄ (567 mm) " ⁄ " (483 mm) 19 "...
  • Page 6: Clearances To Combustibles

    (LIT. TOP) A09681 Fig. 3 - - Clearance to Combustibles If this furnace is installed with a direct- -vent (combustion air and Installer Packet Includes: flue) system, a factory accessory termination kit must be installed. Installation, Startup, and Operating Instructions In a direct- -vent system, all air for combustion is taken directly Service and Maintenance Instructions from the outside atmosphere and all flue products are discharged to...
  • Page 7: Codes And Standards

    General Installation (27º C) S US: NFGC and the NFPA 90B. For copies, contact the National Fire Protection Association Inc., Batterymarch Park, Quincy, MA 02269; or for only the NFGC contact the American Gas Association, 400 N. Capitol, N.W., Washington DC 20001 S CANADA: NSCNGPIC.
  • Page 8: Electrostatic Discharge (Esd) Precautions

    Remove and discard casing drain hole plug button from desired side. The model 355BAV Direct Vent, Upflow, Gas- -Fired, Category IV, h. Install drain tube coupling grommet (factory- -supplied condensing furnace is available in model sizes ranging in input in loose parts bag) in selected casing hole.
  • Page 9 FURNACE BLOWER SHELF CONDENSATE DOOR TRAP CONDENSATE TRAP (INSIDE) FURNACE SIDE (124 mm) FIELD (667 mm) DRAIN (38 mm) ALTERNATE DRAIN CONN TUBE LOCATION SIDE VIEW FRONT VIEW CONDENSATE TRAP DRAIN TUBE LOCATION FACTORY-SHIPPED LOCATION ALTERNATE LOCATION (6 mm) OD 1/ 4 COLLECTOR BOX TO TRAP RELIEF PORT...
  • Page 10: Location

    COLLECTOR BOX TUBE (PINK) PLUG COLLECTOR BOX TUBE (PINK) PLUG INDUCER HOUSING COLLECTOR BOX (MOLDED) DRAIN TUBE (GREEN) TUBE (BEHIND COLLECTOR BOX DRAIN TUBE) COLLECTOR BOX DRAIN TUBE (GREEN) COLLECTOR BOX DRAIN TUBE (BLUE) CONDENSATE TRAP COLLECTOR BOX TUBE (GREEN) CONDENSATE TRAP FIELD-INSTALLED...
  • Page 11 CAUTION UNIT DAMAGE HAZARD This gas furnace may be used for construction heat LEVEL (0”) FRONT provided that: - -The furnace is permanently installed with all electrical 1/2 IN. (13 mm) MAX wiring, piping, air filters, venting and ducting installed according to these installation instructions.
  • Page 12: Low- -Heat Only Installation

    Low- -Heat Only Installation atmosphere, unit must be installed in accordance with This 355BAV furnace can be installed to operate in the low- -heat requirements of National Fire Protection Association, Inc. only heating mode when sized using the low- -heat heating capacity.
  • Page 13: Air Ducts

    that the heat exchanger can be viewed for possible openings using light assistance or a probe can be inserted for sampling the air stream. The cover attachment shall prevent leaks. Ductwork Acoustical Treatment Metal duct systems that do not have a 90 degree elbow and 10 ft. (3.0 M) of main duct to the first branch take- -off may require internal acoustical lining.
  • Page 14: Bottom Closure Panel

    WASHABLE 21-IN. (533mm) WIDE ⁄ -IN. (444mm) WIDE CASINGS ONLY: FILTER CASINGS ONLY: SUPPORT RODS (3) INSTALL FIELD-SUPPLIED EXTEND 1/4" (6mm) ON FILTER FILLER STRIP EACH SIDE OF FILTER AND UNDER FILTER. REST ON CASING FLANGE FILTER RETAINER 3 ″ (76mm) ″...
  • Page 15 WARNING FIRE OR EXPLOSION HAZARD Failure to follow this warning could result in fire, explosion, personal injury, or death. - - Connect gas pipe to furnace using a backup wrench to avoid damaging gas controls. - - Gas valve shutoff switch MUST be facing forward or tilted upward.
  • Page 16: Electrical Connections

    Table 3 – Maximum Capacity of Pipe* WARNING NOMINAL LENGTH OF PIPE --- FT (M) INTERNAL IRON PIPE DIA. SIZE IN. (MM) UNIT MAY NOT OPERATE (3.0) (6.0) (9.1) (12.1) (15.2) IN. (MM) 0.622 1/2 (13) Failure to follow this caution may result in intermittent (158) unit operation.
  • Page 17 FIELD 24-V WIRING FIELD 115-, 208/230-, 460-V WIRING FACTORY 24-V WIRING FACTORY 115-, 208/230-, 460-V WIRING NOTE 5 THERMOSTAT FIVE TERMINALS FIELD-SUPPLIED WIRE DISCONNECT THREE-WIRE HEATING 208/230- OR ONLY 460-V THREE PHASE W/W1 115-V NOTE SINGLE PHASE 208/230-V SINGLE AUXILIARY PHASE 115-V J-BOX...
  • Page 18 Factory Installed J- - Box Location 5. Replace main furnace door and blower access panel. Setup Switches (SW1) Install power entry hole filler plugs (factory- -supplied in loose parts bag) in unused power entry holes. (See Fig. 21.) The furnace control has 8 setup switches that may be set to meet the application requirements.
  • Page 19 A09683 Fig. 23 - - Wiring Diagram...
  • Page 20: Removal Of Existing Furnaces From Common Vent Systems

    NFGC or NSCNGPIC. tests, the venting system must be corrected in accordance The 355BAV can be vented as either a direct vent furnace or as an with the National Fuel Gas Code, ANSI Z223.1/NFPA 54 optional ventilated combustion air application. A direct vent and/or CSA B149.1, Natural Gas and Propane Installation...
  • Page 21 Table 5 – Approved Combustion- -Air and Vent Pipe, Fitting and Cement Materials (U.S.A Only*) ASTM SOLVENT CEMENT AND SPECIFICATION MATERIAL FITTINGS DESCRIPTION PIPE PRIMERS (MARKED ON MATERIAL) D1527 Pipe — — Schedule--- 40 D1785 Pipe — — Schedule--- 40 D2235 For ABS —...
  • Page 22 9. Wipe excess cement from joint. A continuous bead of ce- EXAMPLE: ment will be visible around perimeter of a properly made A 100,000 BTUH furnace located in Indianapolis, elevation joint. 650 ft. (198.1 M) above sea level, could be installed as 10.
  • Page 23 4. Determine the number of combustion air disk halves to be A plugged drain connection has been provided on this fitting for installed in the combustion air intake housing. Insert perfor- use when moisture is found in combustion air intake pipe and ated disk half or assembly (factory supplied in loose parts combustion box.
  • Page 24 This furnace requires OUTDOOR AIR for combustion. WARNING CARBON MONOXIDE POISONING HAZARD The operation of exhaust fans, kitchen ventilation fans, 3˝ (76 mm) clothes dryers, attic exhaust fans or fireplaces could create a NEGATIVE PRESSURE CONDITION at the furnace. Make- -up air MUST be provided for the ventilation devices, Ventilated Combustion Air in addition to that required by the furnace.
  • Page 25 Vent Pipe 5. Install casing hole filler cap (factory- -supplied in loose parts bag) in unused vent pipe casing hole. General Vent Termination Furnace vent connection must be attached as shown in Fig. 25. General WARNING Combustion- -air (direct vent/2- -pipe system only) and vent pipe must terminate outside structure, either through sidewall or roof.
  • Page 26 COMBUSTION-AIR PIPE VENT PIPE COMBUSTION-AIR PIPE 12-IN. MIN (305 mm) 12-IN. MIN VENT PIPE (305 mm) VERTICAL TO ROOF VERTICAL TO SIDEWALL NOTE: A 12 In. (305 mm) minimum offset pipe section is recommended with short (5 to 8 ft / 1.5 to 2.4 M) vent systems. This recommendation is to reduce excessive condensate A06356 Fig.
  • Page 27 Roof Termination (Preferred) Vent Maintain 12 in (305mm) minimum clearance above highest anticipated snow level maximum of 24 in. (610mm) above roof Abandoned masonry used as raceway (per code) 12 in. min. (305 mm)from overhang or roof 6 in. (152mm) minimum clearance between wall and end of vent pipe.
  • Page 28 Multiventing and Vent Terminations with rain shield positioned no more than 1- -in. (25 mm) When 2 or more 355BAV Furnaces are vented near each other, from wall as shown in Fig. 31 and 32. each furnace must be individually vented. NEVER common vent 4.
  • Page 29 FACTORY TEST CONTINUOUS FAN CONNECTOR (CF) AIRFLOW MODEL PLUG SETUP SWITCHES CONNECTOR SW1 SETUP SWITCHES AND BLOWER OFF- DELAY AIR CONDITIONING (A/C) AIRFLOW SETUP SWITCHES HUMIDIFIER TERMINAL (24-VAC 0.5 AMP MAX. ACRDJ AIR CONDITIONING RELAY DISABLE JUMPER 24-V THERMOSTAT TERMINALS STATUS AND COMM LED LIGHTS PL3 ECM BLOWER...
  • Page 30 A05009 Fig. 34 - - Direct Vent Termination Clearance...
  • Page 31 A05013 Fig. 35 - - Other than Direct Vent Termination Clearance...
  • Page 32 Table 8 – Maximum Allowable Pipe Length - - Ft. (M) VARIABLE SPEED VENT SIZING TABLE Direct & Non--- NUMBER OF 90_ ELBOWS Direct Pipe ALTITUDE UNIT SIZE Termination Dia. FT. (M) (BTUH) Type In. (mm)* 2 Pipe or 2 ---In. 1 ---1/2 (38) 50 (15) 45 (14)
  • Page 33: Physical Data

    Table 8 — Maximum Allowable Pipe Length - - Ft./M) (Continued) Variable Speed Vent Sizing Table NUMBER OF 90_ ELBOWS Direct & Non--- ALTITUDE UNIT SIZE Termination Direct Pipe FT. (M) (BTUH) Type Dia. In. (mm)* 2 Pipe or 2 ---In. 1 ---1/2 (38) 35 (11) 30 (9)
  • Page 34: Condensate Drain

    Outdoor draining of the furnace is permissible if allowed by local codes. Caution should be taken when freezing ambient may freeze drain pipe and prohibit draining. CAUTION UNIT MAY NOT OPERATE Failure to follow this caution may result in intermittent unit operation.
  • Page 35: Start- -Up, Adjustments And Safety Check

    1. Remove main furnace door and blower access panel. 2. Locate A/C setup switches on furnace control. (See Fig. 33.) CONDENSATE TRAP 3. Determine air conditioning tonnage used. 4. Use wiring schematic to determine proper setup position of A/C switches. (See Fig. 23 and 39.) NOTE: Excessive airflow caused by improper A/C switch setup may cause condensate blowoff in cooling mode.
  • Page 36 AIR CONDITIONING AIRFLOW* 060 & 080-14 080-20 & 100 120 MODEL TONS (12,000 BTU/HR) (CFM) MODEL MODEL 1-1/2 525 (600) 700 (800) 2-1/2 875 (1000) 1050 (1200) 3-1/2 1225 (1400) 1400 (1600) 1750 (2000) 2100 (2100) X-INDICATES AN ALLOWABLE SELECTION. * Airflow shown in parentheses is airflow unit that the unit will deliver when setup switch SW1-5 is ON (selects 400 CFM/ton) A/C OR CF AIRFLOW SELECTION CHART BASED ON 350 CFM/TON...
  • Page 37: Purge Gas Lines

    The blower door must be installed for power to be conducted through the blower door interlock switch ILK to the furnace control CPU, transformer TRAN, inducer motor IDM, blower motor BLWM, hot- -surface igniter HSI, and gas valve GV. SINGLE- - STAGE THERMOSTAT AND TWO- - STAGE HEATING (ADAPTIVE MODE) See Fig.
  • Page 38 Table 10 – Blower Off Delay Setup Switch Position DESIRED SETUP SWITCH HEATING MODE (SW1---7 AND SW1---8) POSITION BLOWER OFF SW1--- 7 SW1--- 8 DELAY (SEC) 1. Inducer Prepurge Period- -The furnace control CPU turns on inducer motor IDM and slowly increases the inducer motor speed.
  • Page 39 lows: 2. Switching From High- - To Low- - Heat- - If the thermostat Low- -heat- -30 seconds after the gas valve GV- -M is opened, R to W2 circuit opens, and the R to W1 circuit remains the BLWM is turned ON at low- -heat airflow. closed, the furnace control CPU will energize the high- -heat High- -heat- -35 seconds after gas valve GV- -M is opened, the pressure switch relay HPSR to open the NC contact and...
  • Page 40 High- -cooling airflow is based on the A/C selection shown blower- -off delay is decreased from 90 seconds to 5 in Fig. 39. seconds. NOTE: When transitioning from low- -cooling to high- -cooling the Super- - Dehumidify Mode outdoor unit compressor will shut down for 1 minute while the Super- -Dehumidify mode can only be entered if the furnace control furnace blower motor BLWM transitions to run at high- -cooling is in...
  • Page 41 A00275 A00277 Fig. 43 - - Two- -Stage Furnace with Single- -Speed Fig. 45 - - Two- -Stage Furnace with Single- -Speed Air Conditioner Heat Pump (Dual Fuel) A00276 A00278 Fig. 44 - - Two- -Stage Furnace with Two- -Speed Fig.
  • Page 42 A00279 A00281 Fig. 47 - - Dual Fuel Thermostat with Two- -Stage Fig. 49 - - Two- -Stage Thermostat With Two- -Stage Furnace Furnace and Single- -Speed Heat Pump and Two- -Speed Air Conditioner See note 2 A00280 A02348 Fig. 48 - - Dual Fuel Thermostat With Two- -Stage Fig.
  • Page 43 NOTES FOR FIG. 43- - 50: 1. Heat pump MUST have a high pressure switch for dual fuel applications. 2. Refer to outdoor equipment Installation Instructions for additional information and setup procedure. 3. Select the “ZONE” position on the two- -speed heat pump control. 4.
  • Page 44: Adjustments

    Verify furnace model. Table 11 can only be used for changes the timing sequence to avoid long blower off times during model 355BAV Furnaces. demand defrost cycles. Whenever W/W1 is energized along with d. Find installation altitude in Table 11.
  • Page 45 Table 11 – Orifice Size* and Manifold Pressures for Gas Input Rate (Tabulated Data Based on 20,000 Btuh High- -Heat/13,000 Btuh Low- -Heat Per Burner, Derated 2%/1,000 Ft. (305 M) Above Sea Level) A08376A...
  • Page 46 Table 11 — Orifice Size* and Manifold Pressures for Gas Input Rate (Tabulated Data Based on 20,000 Btuh High- -Heat/13,000 Btuh Low- -Heat Per Burner, Derated 2%/1,000 Ft. (305 M) Above Sea Level) (Continued) A08376B...
  • Page 47 REGULATOR COVER SCREW PLASTIC ADJUST SCREW ON/OFF SWITCH REGULATOR SPRING 1/2˝ NPT INLET HIGH STAGE GAS PRESSURE REGULATOR ADJUSTMENT LOW STAGE INLET GAS PRESSURE PRESSURE TAP REGULATOR ADJUSTMENT BURNER ORIFICE MANIFOLD PRESSURE TAP 1/2˝ NPT OUTLET A04167 A93059 Fig. 51 - - Redundant Automatic Gas Valve Fig.
  • Page 48 Table 12 – Altitude Derate Multiplier for U.S.A. ALTITUDE --- FT (M) PERCENT OF DERATE DERATE MULTIPLIER FACTOR* 0–2000(0---610) 1.00 2001–3000 (610---914) 4--- 6 0.95 3001–4000 (914---1219) 6--- 8 0.93 4001–5000 (1219---1524) 8--- 10 0.91 5001–6000 1524---1829) 10--- 12 0.89 6001–7000 (1829---2134) 12--- 14 0.87...
  • Page 49: Check Safety Controls

    Table 13 – Gas Rate Cu Ft/Hr SECONDS SIZE OF TEST DIAL SECONDS SIZE OF TEST DIAL FOR 1 FOR 1 REVOLUTION REVOLUTION cu ft cu ft cu ft cu ft cu ft cu ft 1800 1636 1500 1385 1286 1200 1125 1059...
  • Page 50 4. Set thermostat to “call for heat.” When pressure switches are THERMOSTAT SUBBASE TERMINALS WITH functioning properly, status code 42 will flash on furnace THERMOSTAT REMOVED control approximately 20 sec after thermostat switch is (ANITICIPATOR, CLOCK, ETC., closed. If either a status code 31 or 32 is flashed when in- MUST BE OUT OF CIRCUIT.) ducer motor is disconnected, the furnace will shut itself HOOK-AROUND...
  • Page 51: Checklist

    CHECKLIST — INSTALLATION LOAD CALCULATION ________________ Heating Load (Btuh) Condensate Drain ________________ Cooling Load (Btuh) ________________ Unit Level or Pitched Forward ________________ ________________ Internal Tubing Connections Furnace Model Selection Free of Kinks and Traps ________________ External Drain Connection Leak COMBUSTION AND VENT PIPING Tight and Sloped ________________ Condensate Trap Primed before...
  • Page 52 Catalog No. II355B---40---3 E2010 Bryant Heating & Cooling Systems D 7310 W. Morris St. D Indianapolis, IN 46231 Printed in U.S.A. Edition Date: 08/10 Replaces: II355B--- 40--- 2 Manufacturer reserves the right to discontinue, or change at any time, specifications or designs without notice and without incurring obligations.

Table of Contents