Bryant 355BAV Installation, Start-Up, And Operating Instructions Manual page 11

Direct-vent upflow variable-capacity condensing gas furnace
Hide thumbs Also See for 355BAV:
Table of Contents

Advertisement

LEVEL (0")
TO
1/2 IN. (13 mm) MAX
UPFLOW
Fig. 9 - - Proper Condensate Drainage
S be provided with ample space for servicing and cleaning.
Always comply with minimum fire protection clearances shown
on the furnace clearance- -to- -combustibles label. (See Fig. 3.)
This furnace may be located in a confined space without special
provisions for dilution or ventilation air.
NOTE: Install furnace so that it is level or pitched forward within
1/2- -in. (13 mm) for proper furnace operation. (See Fig. 9.)
When a furnace is installed so that supply ducts carry air circulated
by the furnace to areas outside the space containing the furnace, the
return air shall also be handled by ducts sealed to furnace casing.
The ducts terminate outside the space containing the furnace to
ensure there will not be a negative pressure condition within
equipment room or space.
WARNING
!
FIRE, INJURY OR DEATH HAZARD
Failure to follow this warning could result in fire, property
damage, personal injury, or death.
Do not install furnace on its back. (See Fig. 10.) Safety
control operation will be adversely affected. Never connect
return- -air ducts to back of furnace.
FRONT
BACK
FRONT
Fig. 10 - - Prohibit Installation on Back
FRONT
A06343
B
A
C
K
A93043
CAUTION
!
UNIT DAMAGE HAZARD
This gas furnace may be used for construction heat
provided that:
- -The furnace is permanently installed with all electrical
wiring, piping, air filters, venting and ducting installed
according to these installation instructions. A return air duct
is provided, sealed to the furnace casing, and terminated
outside the space containing the furnace. This prevents a
negative pressure condition as created by the circulating air
blower, causing a flame rollout and/or drawing combustion
products into the structure.
- -The furnace is controlled by a thermostat. It may not be
"hot wired" to provide heat continuously to the structure
without thermostatic control.
- -Clean outside air is provided for combustion. This is to
minimize the corrosive effects of adhesives, sealers and
other
construction
materials.
entrainment of drywall dust into combustion air, which can
cause fouling and plugging of furnace components.
- -The temperature of the return air to the furnace is
maintained between 55_F (13_C) and 80_F (27_C), with
no evening setback or shutdown. The use of the furnace
while the structure is under construction is deemed to be
intermittent operation per our installation instructions.
- -The air temperature rise is within the rated rise range on
the furnace rating plate, and the firing rate has been set to
the nameplate value.
- -The filters used to clean the circulating air during the
construction process must be either changed or thoroughly
cleaned prior to occupancy.
- -The furnace, ductwork and filters are cleaned as necessary
to remove drywall dust and construction debris from all
HVAC system components after construction is completed.
- -After construction is complete, verify furnace operating
conditions including ignition, input rate, temperature rise
and venting, according to the manufacturer's instructions.
The furnace and its return air system shall be designed and installed
so that negative pressure created by the air circulating fan cannot
affect another appliance's combustion air supply or act to mix
products of combustion with circulating air, and that the air
circulating fan of the furnace, if installed in an enclosure
communicating with another fuel- -burning appliance not of the
direct- -vent type, shall be operable only when any door or panel
covering an opening in the furnace fan compartment or in a return
air plenum on ducts is in the closed position.
11
It also
prevents the

Advertisement

Table of Contents
loading

Table of Contents