High Altitude Installations; Non-Combustible Materials Specifi Cation; Combustible Materials Specifi Cation; Electrical Codes - Heat & Glo 6000GBV Owner's Manual

Heat & glo b-vent decorative gas fireplace owner's manual
Hide thumbs Also See for 6000GBV:
Table of Contents

Advertisement

D.

High Altitude Installations

U.L. Listed gas appliances are tested and approved without
requiring changes for elevations from 0 to 2000 feet in the
U.S.A. and Canada.
When installing this appliance at an elevation above 2000
feet, it may be necessary to decrease the input rating by
changing the existing burner orifi ce to a smaller size. Input
rate should be reduced by 4% for each 1000 feet above
a 2000 foot elevation in the U.S.A., or 10% for elevations
between 2000 and 4500 feet in Canada. If the heating
value of the gas has been reduced, these rules do not
apply. To identify the proper orifi ce size, check with the
local gas utility.
If installing this appliance at an elevation above 4500 feet
(in Canada), check with local authorities.
WARNING
Do NOT use this appliance if any part has been under water.
Immediately call a qualifi ed service technician to inspect
the appliance and to replace any part of the control system
and any gas control which has been under water.
E. Non-Combustible Materials Specifi cation
Material which will not ignite and burn. Such materials are
those consisting entirely of steel, iron, brick, tile, concrete,
slate, glass or plasters, or any combination thereof.
Materials that are reported as passing ASTM E 136,
Standard Test Method for Behavior of Materials in
a Vertical Tube Furnace at 750
non-combustible materials.
F. Combustible Materials Specifi cation
Materials made of or surfaced with wood, compressed pa-
per, plant fi bers, plastics, or other material that can ignite and
burn, whether fl ame proofed or not, or whether plastered or
unplastered shall be considered combustible materials.
G. Electrical Codes
NOTICE: This appliance must be electrically wired and
grounded in accordance with local codes or, in the absence
of local codes, with National Electric Code ANSI/NFPA
70-latest edition or the Canadian Electric Code CSA
C22.1.
• A 110-120 VAC circuit for this product must be protected
with ground-fault circuit-interrupter protection, in
compliance with the applicable electrical codes, when
it is installed in locations such as in bathrooms or near
sinks.
o
C, shall be considered
Heat & Glo • 6000GBV, 6000GBV-IPI • 2104-900 Rev. G • 9/08
5

Advertisement

Table of Contents
loading

This manual is also suitable for:

6000gbv-ipilp6000gbv-ipi6000gbv-lp

Table of Contents