Connecting the cable
UH105/140CAV
UH070CAV1
Example of Air Conditioner System
When using ELB for 1 phase
If an outdoor unit is installed in a place in danger of an electric leak or submergence, you must install the ELB.
Power Cable Specifications
Outdoor
UH070CAV1
UH105CAV
UH140CAV
The power cable is not supplied with air conditioner.
For power cable, use the grade H07RN-F or H05RN-F materials.
10
E-
Two electronic cables must be connected to the outdoor unit.
The connection cord between indoor unit and outdoor unit.
The power cable between outdoor unit and auxiliary circuit breaker.
Be sure to run the power supply cable and the communication cable through
electrical conduit as seen in the picture .
Protect the power and communication cable using the protection tube indi
vidually.
Make a knockout hole.
After making a knockout hole ,apply rust resisting paint around the hole.
Secure the cable tube to the outdoor knockout using the CD connector and
bushing.
Conduit
CAUTION
D uring the unit installation make first refrigerant connections and then
electrical connections. If unit is uninstalled first disconnect electrical
cables, then refrigerant connections.
Conduit
C onnect the air conditioner to grounding system before performing the
electrical connection.
Outdoor Unit
Grounding
power cable
Power supply
inch²(mm²),wires
0.007inch²(4mm²), 2
1Φ, 208-230V~/60Hz
0.013inch²(4mm²), 2
0.019inch²(6mm²), 2
Communication cable
Power cable
Indoor Unit
MAX. LENGTH
ft(m)
<32.8 ft(10m)
Power cable
Communication cable
Type GL
A
30
30
40