INSTALLATION
MANUAL
UH070CAV1
UH105CAV
UH140CAV
System Air Conditioner
(Cooling and Heating)
E
S
F DB98-29516A(3)

Advertisement

Table of Contents
loading

Summary of Contents for Samsung UH070CAV1

  • Page 1 INSTALLATION MANUAL UH070CAV1 UH105CAV UH140CAV System Air Conditioner (Cooling and Heating) F DB98-29516A(3)
  • Page 2: Safety Precautions

     This manual explains how to install an indoor unit with a split system with two SAMSUNG units. The use of other types of units with different control systems may damage the units and invalidate the warranty. The manufacturer shall not be responsible for damages arising from the use of non compliant units.
  • Page 3: Table Of Contents

    Contents Preparation for outdoor unit installation ....... . 4   Deciding on where to install the outdoor unit .
  • Page 4: Preparation For Outdoor Unit Installation

    Preparation for outdoor unit installation The air conditioner uses R410A refrigerant. Type A : UH105CAV/UH140CAV 4- 12  Heat pump Type B : UH070CAV1  Heat pump 312.6 52.9...
  • Page 5 Moving the Outdoor Unit by Wire Rope Wire rope Fasten the outdoor unit by two 8m or longer wire ropes as shown at the figure. To prevent from damage or scratches, insert a piece of cloth between the outdoor unit and rope, then move the unit. Plate protection cloth...
  • Page 6: Deciding On Where To Install The Outdoor Unit

    Deciding on where to install the outdoor unit Outdoor Unit  The outdoor unit must not be placed on its side or upside down, as the compressor lubrication oil will run into the cooling circuit and seriously damage the unit. ...
  • Page 7 Space Requirements for Outdoor Unit When installing 1 outdoor unit Unit : mm  When the air outlet is opposite the wall  When the air outlet is towards the wall 2000 or more 300 or more 600 or more ...
  • Page 8 Deciding on where to install the outdoor unit (Continued) When installing more than 1 outdoor unit Unit : mm  When the air outlet is towards the wall 300 or more 600 or more 600 or more 600 or more ...
  • Page 9: Outdoor Unit Installation

    Outdoor unit installation The outdoor unit must be installed on a rigid and stable base to avoid any increase in the noise level and vibration, particularly if the outdoor unit is to be installed in a location exposed to strong winds or at a height, the unit must be fixed to an appropriate support(wall or ground).
  • Page 10: Connecting The Cable

      Secure the cable tube to the outdoor knockout using the CD connector and bushing. Conduit UH070CAV1 CAUTION  D uring the unit installation make first refrigerant connections and then electrical connections. If unit is uninstalled first disconnect electrical cables, then refrigerant connections.
  • Page 11 Wiring Diagram of Power Cable When using ELB for 1 phase Power Supply  Outdoor unit Electrical component box MCCB MCCB Communication Cable cable clamp Connection cord Main power cable Indoor Unit CAUTION  Y ou should connect the power cable into the power cable terminal and fasten it with a clamp.
  • Page 12: Connecting The Power Terminal

    Connecting the cable (Continued) Wiring Diagram of Connection Cord Indoor Unit 1(L) 2(N) VC VC F1 F2 V1 V2 F3 F4 Outdoor Unit 1(L) 2(N) Outdoor Unit Note Ground wire for the indoor unit and outdoor unit connection cable must be clamped to a soft copper tin-plated eyelet terminal with M4 screw hole(NOT SUPPLIED WITH UNIT ACCESSORIES).
  • Page 13: Connecting The Refrigerant Pipe

    Connecting the refrigerant pipe Refrigerant Piping System Pipe length or height Refrigerant piping system table UH105CAV UH070CAV1 UH140CAV Max. allowable Actual pipe L0 + H + L1 164.04ft(50m) or less 246.06ft(75m) or less length length Allowable Actual pipe 98.43ft(30m) or less 98.43ft(30m)
  • Page 14: Connecting Up And Removing Air In The Circuit

    Connecting up and removing air in the circuit...
  • Page 15: Cutting/Flaring The Pipes

    Cutting/Flaring the pipes Make sure that you have the required tools available. (pipe cutter, reamer, flaring tool and pipe holder) If you wish to shorten the pipes, cut it with a pipe cutter, taking care to ensure that the cut edge remains at a 90° angle with the side of the pipe. Refer to the illustrations below for examples of edges cut correctly and incorrectly.
  • Page 16: Performing Leak Tests

    Performing leak tests Connecting the drain hose to the outdoor unit Insulation No gap 0.511inch NBR(T or thicker)
  • Page 17: Using Stop Valve

    Using stop valve To Open the Stop Valve Open the cap and turn the stop valve counterclockwise by using a hexagonal wrench. Service port Turn it until the axis is stopped. Note Do not apply excessive force to the stop valve and always use ...
  • Page 18: Adding Refrigerant

    Adding refrigerant The outdoor unit is loaded with sufficient refrigerant for the standard piping. Thus, refrigerant must be added if the piping is lengthened. This operation can only be performed by a qualified refrigeration specialist. For quantity of adding refrigerant, refer to page 19. Check that the stop valve is closed entirely.
  • Page 19 The quantity of additional refrigerant is variable according to the installation situation. Thus, make sure the outdoor unit situation before adding refrigerant. This operation can only be performed by a qualified refrigeration specialist. Model “Q”(R410A) “P” UH070CAV1 0.32oz/ft (30g/m) 16.4ft(5.0m) UH105CAV 0.43oz/ft (40g/m) 24.6 ft(7.5m) UH140CAV 0.43 oz/ft (40g/m)
  • Page 20: Transmitter Installation (Optional)

    If you install a transmitter to an outdoor unit, every indoor unit which is connected to an outdoor unit can be controlled simultaneously. Each outdoor unit connected to the same centralized controller has its own transmitter. UH105/140CAV UH070CAV1 Plate Control Low Transmitter Terminal side Transmitter Bolts spec.
  • Page 21: Pump Down Procedure

    Pump down Procedure Pump down will be carried out when an evaporator is replaced or when the unit is relocated in another area. Remove the cap from the low pressure side. Turn the low pressure side valve clockwise to close and connect a pressure gauge (low pressure side) to the service valve, and open the valve again.
  • Page 22: Checking Correct Grounding

    Checking correct grounding If the power distribution circuit does not have a grounding or the grounding does not comply with specifications, an grounding electrode must be installed. The corresponding accessories are not supplied with the air conditioner. Select an grounding electrode that complies with the specifications given in the illustration.
  • Page 23: Testing Operations

    Testing operations Check the power supply between the outdoor unit and the auxiliary circuit breaker. Rotary Single phase power supply: L, N  Switch ���� ���� Check the indoor unit. Switch 2-1 Check that you have connected the power and communication ����...
  • Page 24: Troubleshooting

    Troubleshooting The table below give indication about self diagnostic routine. Some of error code requires activities exclusively for Authorized Service Center. Outdoor unit If an error occurs during the operation, it is displayed on the outdoor unit PCB. Product operation status in case of error Display Content...
  • Page 25: Display Content

    Product operation status in case of error Display Content Measure Error type Outdoor unit compressor/ Outdoor unit fan Non-connection error Self Diagnosys of indoor and outdoor Check the status of power connection- Error Communication wire Check the connection status of the Operation Off (connected to the power communication line...