Testing operations
1
Check the power supply between the outdoor unit and the auxiliary circuit
breaker.
Single phase power supply: L, N
2
Check the indoor unit.
2-1 Check that you have connected the power and communication
cables correctly. (If the power cable and communication cables one
mixed up or connected incorrectly, the PCB will be damaged.)
2-2 Check the thermistor sensor, drain pump/hose, and display are
connected correctly.
3
Press K1 & K2 on the outdoor unit PCB the system will follow this sequence:
K1 push one start Heating test mode K1 push two test mode stop
K2 push one start Cooling test mode K2 push two test mode stop
4
After 12 minutes of stationary condition check each indoor unit air treatment :
C ooling mode(indoor unit check)Inlet air temp. - Outlet air temp. :
From
50°F(10°C) to 53.6°F(12°C)
H eating mode(indoor unit check)Outlet air temp. - Inlet air temp. :
From
51.8°F(11°C) to 57.2°F(14°C)
I n heating mode, the indoor fan motor can remain off to avoid cold air
blown into conditioned space.
Settings of PCB Display of the Outdoor unit
K1
K2
KEY
CHECK
MODE
Function
Number of
press times
Test operation at
1
2
K3
K4
RESET
DISPLAY
MODE
K1
K2
Test operation at
heating mode
cooling mode
End
End
Rotary
Switch
DIP
Switch
Note
Rotary Switch must be adjusted to"0"position .
DIP Switch must be adjusted to "ON" position .
DIS 1
Display
ITEM NO.
K3
Reset
-
����
����
����
����
DIS 2
CURRENT DATA DISPLAY
K4
Displays Data
-
23
E-