Wiring Diagram of Power Cable
When using ELB for 1 phase
Power Supply
Electrical component box
MCCB
ELB
MCCB
Indoor Unit
CAUTION
Y ou should connect the power cable into the power cable terminal and
fasten it with a clamp.
The unbalanced power must be maintained within 2% of supply rating.
- If the power is unbalanced greatly, it may shorten the life of the condenser.
If the unbalanced power is exceeded over 4% of supply rating,
the indoor unit is protected, stopped and the error mode indicates.
To protect the product from water and possible shock, you should keep the
power cable and the connection cord of the indoor and outdoor units in the
iron pipe.
Ensure that main supply connection is made through a switch that disconnects
all poles, with contact gap of a least
Must keep the cable in a protection tube.
Keep distances of
1.968 inch(50 mm)
munication cable.
Outdoor unit
Communication
cable
Connection cord
0.118 inch(3
mm).
or more between power cable and com-
Cable
clamp
Main power cable
11